Operation Manual 37107F
MFR 3 - Multi Function Relay
© Woodward
Page 133/165
Start Counter
Parameter
247
Start counter
ON
Start counter
ON/OFF
ON
................ Start counter is enabled. Refer to Parameter 248 for a description.
OFF
.............. The counter is not enabled.
NOTE
After 32,000 starts, the counter is automatically reset.
Parameter
248
Start counter
set 00000
Start counter: value
0 to 32,000
The start counter is used to display how many times the engine has been started.
Following each starting attempt the start counter is increased by one. This permits
the user to display the correct number of starts if this controller is used on an older
engine, a starter is replaced, or this controller is to replace an older controller.
Only maintenance personnel should configure the start counter!
NOTE
If the control unit number of starts must be configured to a specific value, the unit must be in code lev-
el 2 in order to achieve this. The counter is reset in a 2-step procedure for safety reasons. The follow-
ing procedure applies:
1. Step: Configure and store the desired number of starts.
2. Step: Integration of the value which has been saved:
1. Exit the configuration mode and switch the controller into AUTOMATIC mode
2. Navigate to the display screen "
Start counter 00000
" using the "Select" button
3. Press and hold the "Digit" push button for 7 seconds
kWh/kvarh Counter
Parameter
249
Display kWh +-
on? YY
Display kWh counter
Y/N
It is possible to display the positive kWh counter (+) and/or the negative kWh
counter (-) by selecting "Y" or "N". It is possible to display no counters, one coun-
ter or both counters by making the appropriate entry
Y
................... The selected kWh counter is visible.
N
................... The selected kWh counter is not visible.
Parameter
250
Display kvarh +-
on? YY
Display kvarh counter
Y/N
It is possible to display the inductive kvarh counter (+) and/or the capacitive kvarh
counter (-) by selecting "Y" or "N". It is possible to display no counters, one coun-
ter or both counters by making the appropriate entry.
Y
................... The selected kvarh counter is visible.
N
................... The selected kvarh counter is not visible.
Resetting the Counters
Resetting the counters (start counter, operating hours counter, kWh counter, kvarh counter) must be performed in
code level 2.
To reset the individual counters, the control unit must be in the AUTOMATIC mode. Navigate to the display
screen that is to be reset or changed. Press and hold the "Digit" button for at least 7 seconds.
For the start counter and the operating hours counter, the values that have been configured in the parameters
"Start counter set" or "Op.hours counter set” will be integrated into the display.