Operation Manual 37107F
MFR 3 - Multi Function Relay
Page 132/165
© Woodward
Operating Hours Counter
Parameter
245
Op.hours counter
ON
Operating hours counter
ON/OFF
ON
................ Operating hours counter is enabled. Refer to Parameter 246 for a de-
scription.
OFF
.............. The counter is not enabled.
NOTE
The operating hours counter can be set to a maximum value of 65,000 hours.
Parameter
246
Op.hours counter
set 00000h
Operating hours counter: value
0 to 65,000 h
This parameter can be used to specify the number of hours an engine has been in
operation. This permits the user to display the correct number of engine hours if
this controller is used on an older engine or this controller is to replace an older
controller.
NOTE
If the control unit operating hours must be configured to a specific value, the unit must be in code lev-
el 2 in order to achieve this. The counter is reset in a 2-step procedure for safety reasons. The follow-
ing procedure applies:
1. Step: Configure and store the desired operating hours.
2. Step: Integration of the value which has been saved:
1. Exit the configuration mode and switch the controller into AUTOMATIC mode
2. Navigate to the display screen "
Op.hours 000h
" using the "Select" button
3. Press and hold the "Digit" push button for 7 seconds