Sensor
Description
Remark
14 Reserved
Fuel Level
Sensor
0 Not used
1 User configured (Resistance)
2 SGH
3 SGD
4 to 5 Reserved
6 DIGITAL CLOSED
7 DIGITAL OPEN
Defined range of resistance is (0 to 6) KΩ.
Default is »0 Not used«.
Configuration/Setting
When reselecting sensors, the sensor curve will be transferred to the standard value. For
example, if a temperature sensor is SGX (120°C resistor type), its sensor curve is SGX
(120°C resistor type); if you select the SGD (120°C resistor type), the temperature sensor
curve is SGD curve.
If there is a difference between standard sensor curve and used sensor, it can be
adjusted in the “curve type” menu.
When entering the the sensor curve values, the X value (resistor) must be in sequence
from small to large, otherwise, mistakes can occur.
If you select the option None under sensor type, the sensor curve does not work.
If the corresponding sensor has an alarm switch only, set this sensor to “None”.
Otherwise, shutdown or warnings can occur.
4.3.2
Programmable Inputs
The programmable inputs are all active, if connected to ground (B-).
Each input needs an alarm type and a release condition definition:
No.
Items
Description
0
Not Used
1
High temperture shutdown
If the signal is active after safety run on delay over, the genset will
immediately activate a shutdown alarm.
2
Low oil pressure shutdown
3
Warning alarm
Only warning, no shutdown.
4
Shutdown alarm
If the signal is active, genset will immediately alarm to shutdown.
59
easYgen-400
B37884A
4 Configuration
4.3.2 Programmable Inputs
Released