CAUTION!
Set factory default settings causes easYgen power cycle!
Don't run "Set factory default values"
during controlling a genset because it
causes a power cycle of the easYgen control.
The default values shall be reset.
• Modbus address = 40000 + (Par. ID + 1) = 41702
•
• Modbus length = 1 (UNSIGNED 16)
•
⚙
ᐳ
Fig. 324:
Modscan32 at address 410418
1. ▷
Use the "display options" to set the value format to decimal.
2. ▷
Double-click the address to issue a
Write Register
command.
▶
Fig. 325:
Write register - resetting the default values
shows how the parameter is enabled using the ModScan32 Software. The
value must be set to "1" to enable the parameter.
6.5.3
Exception Responses
The Modbus protocol has multiple exception responses to show that a request could not
be executed. Exception responses can be recognized if the response telegram contains
the request function code with an offset of 128 (0x80 hex).
explains possible reasons for an exception response that occurred.