Bit “x” of
Parameter
504 ...
... remotely
requests to switch
to
... is available as LogicsManager
command variable
... uses LogicsManager “y”
to switch
Bit 6
Power factor setpoint
2
"04.39 Remote PF setp. 2"
12921: "86.84 LM: Setp.2
pwr.factor"
Bit 7
Active power setpoint
2
"04.40 Remote pwr. setp. 2"
12919; "86.82 LM: Setp. 2 load"
12998; "87.67 LM: Setp. 3 load"
12969; "87.75 LM: Setp. 4 load"
Notes
This LogicsManager command
variable can be used to switch
to each available load setpoint.
☼
Example
Fig. 298:
Remotely switch Setp. 2 load
The active power setpoint 2 is to be enabled. Therefore LM 12919 is prepared using
04.40 (see beside).
The switching signal than comes remotely e.g. as described below:
• Modbus address = 40000 + (Par. ID + 1) = 40505
•
• Modbus length = 1 (UNSIGNED 16)
•
⚙
ᐳ
To set the bits in ModScan32:
1. ▷
Fig. 299:
ModScan32 single bit view
Using the "display options" set the format to binary to view single bits (
2. ▷
Double-click the address to issue a
Write Register
command.
799
easYgen-3000XT Series
B37574
6 Application Field
6.5.1.3 Remotely Changing The Setpoint
Released