ID
Parameter
CL
Setting range
[Default]
Description
not present within the delay
configured in parameter
, the MCB will be opened as
well.
MCB
Mains decoupling is carried out
according to the following
parameters. If one of the
subordinate monitoring functions
is triggered, the MCB will be
opened.
MCB->GCB
Mains decoupling is carried out
according to the following
parameters. If one of the
subordinate monitoring functions
is triggered, the MCB will be
opened. If the reply "MCB open" is
not present within the delay
configured in parameter
, the GCB will be opened as
well.
GCB/MCB by LM
Mains decoupling is carried out. If
one of the subordinate monitoring
functions is triggered, a breaker
will be opened, which is
determined by the LogicsManager
equation "
decoupling MCB". If it's status is
TRUE, the MCB will be opened. If
it's status is FALSE, the GCB will
be opened.
15160
Mains decoupl.MCB
2
Determined by LogicsManager
87.73
[(0 & 1) & 1]
FALSE: If the decoupling is
triggered, the GCB will be opened.
TRUE: If the decoupling is
triggered, the MCB will be opened.
Only available in Mains decoupling
mode "GCB/MCB by LM".
3113
Mns. decoupling
feedback delay
2
0.2 to 99.9 s
[0.4 s]
If the open signal from the
respective circuit breaker cannot
be detected within the time
configured here, the mains
decoupling function performs the
action as configured in
parameter
3111
Alarm class
2
Class A, Class B, Class C, Class D,
Class E, Class F , Control
[Class B]
Each limit may be assigned an
independent alarm class that
specifies what action should be
taken when the limit is surpassed.
Notes
For additional information refer to
.
3112
Self acknowledge
2
Yes
The control automatically clears
the alarm if the fault condition is
no longer detected.
[No]
The control does not automatically
reset the alarm when the fault
condition is no longer detected.
491
easYgen-3000XT Series
B37574
4 Configuration
4.5.3.4 Mains Decoupling