ID
Parameter
CL
Setting range
[Default]
Description
55% (50% of the difference
between 70 and 40%)
• High:
•
Load level before stopping:
31.25%
Resulting load level for
remaining engine:
62.5% (75% of the difference
between 70 and 40%)
5764
IOP Add on delay
2
0 to 32000 s
[10 s]
Load swings may exceed the
threshold momentarily. In order to
prevent the engine from starting
due to short-term load swings, a
delay time may be configured.
The LDSS criterion for adding load
must be exceeded without
interruption for this delay time,
configured in seconds, prior to a
start command being issued.
If the LDSS criterion for adding
load is fallen below before the
delay time expires, the delay time
is reset and a start command is
not issued.
5765
IOP Add on delay at
rated load
2
0 to 32000 s
[3 s]
The command to start the next
genset in case a genset exceeds
rated load will be issued after the
delay configured here has expired.
Notes
This parameter becomes only
effective in case a genset exceeds
rated load to achieve a faster start
and overrides parameter
.
5766
IOP Add off delay
2
0 to 32000 s
[60 s]
Load swings may fall below the
threshold momentarily. In order to
prevent the engine from stopping
due to short-term load swings, a
delay time may be configured.
The load must remain below the
hysteresis setpoint without
interruption for the delay time,
configured in seconds, prior to a
stop command being issued.
If the load exceeds the hysteresis
setpoint before the delay time
expires, the delay time is reset
and a stop command is not
issued.
409
easYgen-3000XT Series
B37574
4 Configuration
4.4.5.5.4 Islanded Parallel Operation (IOP)