ID
Parameter
CL
Setting range
[Default]
Description
Notes
This parameter only applies to
application modes
A03
and
A04
.
3405
GCB auto unlock
2
This is used for special circuit
breakers to put the GCB into a
defined initial state or to enable
closing at all.
Yes
Before every close-pulse, an open-
pulse is issued for defined
duration (parameter
CB close pulse is enabled only
after the open pulse is issued.
[No]
The CB close pulse is enabled
without being preceded by a CB
open pulse.
Notes
This parameter only applies to
application modes
A03
and
A04
.
5708
GCB open time pulse
2
1.00 to 10.00 s
[1.00 s]
This time defines the length of the
GCB open time pulse, if the
automatic switch unblocking GCB
is activated.
Notes
This parameter only applies to
application modes
A03
and
A04
.
12887
Enable GCB
2
Determined by LogicsManager
86.95
[(1 & 1) & 1]
= 12051
If active the closure of the GCB is
enabled otherwise the GCB
closure is disabled
Notes
Changing the state will cause an
entry in the event list.
If disabled, status "GCB closure
disabled" alternating with "In
operation" will be indicated.
12886
Open GCB
immediately
2
Determined by LogicsManager
86.51
[(0 & 1) & 1]
= 12052
Once the conditions of the
LogicsManager have been fulfilled
the GCB will be opened
immediately.
Notes
The "Open GCB immediately" has
a higher priority than the Enable
GCB function and is valid for all
application and operating modes.
284
easYgen-3000XT Series
B37574
4 Configuration
4.4.3.3 Configure Breakers: GCB
Released