Characteristic
Fig. 63:
MPU - characteristic
shows the minimal necessary input voltage depending on frequency. It is
recommended to ensure input voltage greater than minimal necessary with a margin of 2
to 3 V (especially at high ambient temperature above +50 °C).
3.3.10
Discrete Inputs
General notes
WARNING!
Hazards due to improper implementation of emergency stop
Discrete input [DI 01] "Emergency Stop" is only a signaling input. This input may only be
used to signal that an external emergency stop button has been actuated.
According to EN 60204, this input is not approved to be used as the emergency stop
function.
• The emergency stop function must be implemented external to the control and
•
cannot rely on the control to function properly.