Example for test without load: The engine shall start once a month and run for one hour without overtaking the
load. The test day shall be every fifteenth of a month (with flag 2). A relay output can be configured that this test
is running, e.g. for a signal lamp.
The following settings are to be made for the timer:
ID
Parameter
Value
Comment
1663
Active day
15
The active day is enabled every fifteenth of the month
1662
Active hour
10
The active hour is enabled between 10:00 and 11:00 am every day
Table 4-6: Timer configuration
The
LogicsManager
function Flag 2 (parameter ID 12240) can be configured as shown in Figure 4-10. Flag 2 be-
comes TRUE as soon as the configured active day and active time is reached.
Figure 4-10: Configuration – Flag 2 (timer)
The Start without load
LogicsManager
function (parameter ID 12540) can be configured as shown in Figure
4-11. Start without load mode is enabled as soon as Flag 2 becomes TRUE.
Figure 4-11: Configuration - Start w/o load