If the speed sensor (»Firing speed RPM«) is not selected, the rotating speed displayed on
the controller is calculated from generator frequency and the number of poles.
If the generator frequency (»Firing speed Hz«) is not selected, the relative power quantity
will neither be registrated nor displayed (e.g. water pump application).
HMI only! In ToolKit-SC frequency, speed, and oil pressure can be enabled/
disabled separately; HMI is using a table »Firing speed« instead:
No.
Setting description
0
Gen frequency
1
Speed sensor
2
Speed Gen frequency
3
Oil pressure
4
Oil pr Gen frequency
5
Oil pr Speed sensor
6
Oil pr Speed Gen frequency
3.5.2
Manual Breaker Transition
When the controller is in MANual mode, the procedures to switch supply between mains
and genset will be started by a manual process when the breaker switch is pressed.
CAUTION!
Neither mains nor generator state is taken into account. Breaker open/close works
independent from the load.
If the generator or the mains are "out of range", the load can be damaged!
Both breakers GCB and MCB open:
Taking load
Press the breaker switch
The respective breaker is closed.
The closing signal will last for the »Closing time«
During this time, all other breaker signals are suppressed.
23
easYgen-1700
37888A
3 Operation
3.5 Transition Procedures