Application 

Supervision of DC voltages 
 
 

Function 

Unit BU1-DC2 is equipped with an over- (U>) and undervoltage supervision (U<) with separate ad-
justable pick-up values and common trip delay (t) and hysteresis (DIFF). 
The DC voltage measured is constantly compared with the set reference values. Any voltage sig-
nal, which exceeds the set reference value for overvoltage, or falls below the set reference value 
for undervoltage, will cause the respective relay to trip after elaps of the time delay. 
Pick-up of the supervision circuit, either U> or U<, is displayed by the corresponding flashing LED. 
At undervoltage tripping LED U< extinguishes. At U>-tripping LED U> is steady lit. 
 
 

Technical data 

rated voltage Un: 

 

 

 

12 V or 24 V 

Power 

consumption: 

   3 

dropout to pickup ratio:   

 

 

dependent on the set hysteresis 

dropout 

time: 

    300 

ms 

Minimum operating delay: 

 

 

300 ms 

 

Output relay 

max. breaking capacity:  

 

 

ohmic 250 V AC/120 V DC 

      inductive 

500 

AC/ 

75 

DC 

rated 

current: 

    5 

making 

current: 

    20 

 

System Data 

regulations: 

    VDE 

0435 

part 

303 

temperature range at  
storage and operation:   

 

 

-25°C to 70°C 

 

Mechanical stress: 

shock:   

 

 

 

 

class 1 acc. to DIN IEC 255-21-2 

vibration: 

 

 

 

 

class 1 acc. to DIN IEC 255-21-1 

 

degree of protection 

unit front: 

 

 

 

 

IP 40 at closed front cover 

weight: 

     approx. 

0.3 

kg 

mounting 

position: 

   any 

 
 

 

DOK-TD-BU1-DC2E Rev.A 