3 & 5 HP Governor Test Stand

Woodward 

19

 Air from the vacuum generator is exhausted to the table drain area. Oil from the

exhaust tube is an indication of an oil leak in the governor being tested. The
vacuum generator may be removed from the stand and washed with ordinary
shop solvents. Disassembly of the generator should not be necessary.

The vacuum accessory is designed to provide the vacuum needed to check
limiters and lube-oil vacuum trips. The vacuum accessory is not designed to
move oil or help in keeping the test stand clean and must not be used for this
purpose, as excessive dirt or oil will plug the orifice in the venturi vacuum pump.

Variable DC Power Supply (8272-618)

The variable power supply provides 10 to 140 Vdc power to permit testing
electric speed-setting and solenoid devices used on many governors. The power
supply is necessary to use the PGE (rail governor) switch set which mounts on
the operator control panel. The device may also be used to test the mechanical
side of EGB units.

Figure 4-2. Variable DC Power Supply

Located in the center of the back panel, the optional device converts 110 Vac
power to dc voltage. A three-position switch provides variable dc output up to 140
Vdc to the optional PGE switch set when in the up (Internal) position. In the
center position, no voltage is available from the dc option. In the lower (external)
position, the output of the option is between 10 and  140 Vdc as set with the
potentiometer and read on the digital voltmeter.

The external output is available only at the (+) and (–) jacks on the back panel,
and no voltage is available from the switch set. A 2.5 A fuse protects the dc
supply.

110 Volt Plug

 A 110 V, single-outlet plug is provided on the side of the test stand for the

convenience of the operator. The plug is protected by a 3 A "SloBlo" fuse.

Summary of Contents for 8909-051

Page 1: ...ons Original Instructions Governor Governor Te Test Stand st Stand Mod Model 8909 el 8909 05 051 3 1 3 Hor Horsep sepow ower 2 2 er 2 2 kW kW Mod Model 8909 el 8909 05 053 5 3 5 Hor Horsep sepow ower...

Page 2: ...vision be sure to c you have the latest revision be sure to c heck the heck the publications page publications page on on the Woodward website the Woodward website www woodward com publications www wo...

Page 3: ...15 15 Drive Boards Drive Boards 16 16 C CHAPTER HAPTER 4 4 A ACCESSORIES CCESSORIES 17 17 Introduction 17 Introduction 17 Universa Universal l Accessorie Accessories s 17 17 C CHAPTER HAPTER 5 5 G GO...

Page 4: ...ents CHAPTER 8 PRODUCT SUPPORT AND SERVICE OPTIONS 64 Product Support Options 64 Product Service Options 64 Returning Equipment for Repair 65 Replacement Parts 65 Engineering Services 66 Contacting Wo...

Page 5: ...Stand Connections for UG Governors 31 Figure 5 5 Test Stand Connections for SG PSG and TG Governors 32 Figure 5 6 Test Stand Connections for EGB Governors 33 Figure 5 7 Connections for EGB and PG 200...

Page 6: ...3 5 HP Governor Test Stand Manual 25805 iv Woodward...

Page 7: ...utput shaft of the actuator or governor under test The monofilament line is then attached to the universal lever with the take up spool either 20 degrees before the maximum stop or 20 degrees in front...

Page 8: ...RT button can activate the drive circuit Increase Gain Sensitivity This potentiometer turned counterclockwise retards the rate of response of the test stand drive motor to a speed change On initial op...

Page 9: ...elect the drive adapter with the proper serration or keyway and the drive coupling if needed for the test stand motor Select the proper pilot adapter plate to fit the governor base to the stand Clamp...

Page 10: ...rs Universal Accessories Air Pressure Vacuum Accessories Many Electric Test Stands feature an optional air pressure vacuum accessory panel The air pressure system accepts a maximum of 200 psi 1380 kPa...

Page 11: ...ft side of the stand Also available with a dual regulator and selector valve part number 6995 975 0 120 Inches of Mercury Air Pressure Gauge 8959 057 6 inch 152 mm diameter accuracy at 0 1 Mounted on...

Page 12: ...ces used on many governors The power supply is necessary to use the PGE rail governor switch set which mounts on the operator control panel The device may also be used to test the mechanical side of E...

Page 13: ...Manual Manual 258 25805 05 3 3 5 5 HP HP Governor Governor Test Test Stand Stand Woodward 29 Woodward 29 Figure 5 2 PGA Connections Figure 5 2 PGA Connections...

Page 14: ...3 3 5 5 HP HP Governor Governor Test Test Stand Stand Manual Manual 258 25805 05 30 Woodward 30 Woodward Figure 5 3 PG Lever PG Dial PG PH Connections Figure 5 3 PG Lever PG Dial PG PH Connections...

Page 15: ...ual Manual 258 25805 05 3 3 5 5 HP HP Governor Governor Test Test Stand Stand Woodward 31 Woodward 31 Figure 5 4 Test Stand Connections for UG Figure 5 4 Test Stand Connections for UG Governors Govern...

Page 16: ...3 5 HP Governor Test Stand Manual 25805 32 Woodward Figure 5 5 Test Stand Connections for SG PSG and TG Governors...

Page 17: ...Manual 25805 3 5 HP Governor Test Stand Woodward 33 Figure 5 6 Test Stand Connections for EGB Governors...

Page 18: ...3 5 HP Governor Test Stand Manual 25805 34 Woodward Figure 5 7 Connections for EGB and PG 200 300 and 500 Governors...

Page 19: ...upply 1 Screw 4 40 x 250 4 25805 202 12 Volt Relay 1 8 Pin Surface Mount Socket 1 Screw 6 32 x 500 2 25805 203 Feedback Amp Board Assembly 1 Nut 6 32 Elastic Hex 4 Jumper 2 Section Terminal Block 1 25...

Page 20: ...d also be handled through the OEM or Packager Please review your equipment system documentation for details Woodward Business Partner Support Woodward works with and supports a global network of indep...

Page 21: ...s option is applicable to mechanical products only Returning Equipment for Repair If a control or any part of an electronic control is to be returned for repair please contact your Full Service Distri...

Page 22: ...mation on these services please contact one of the Full Service Distributors listed at www woodward com directory Contacting Woodward s Support Organization For the name of your nearest Woodward Full...

Page 23: ...ype of Fuel gas gaseous diesel dual fuel etc Power Output Rating Application power generation marine etc Control Governor Information Control Governor 1 Woodward Part Number Rev Letter Control Descrip...

Page 24: ...t Drake Road Fort Collins CO 80525 USA Phone 1 970 482 5811 Fax 1 970 498 3058 Email and Website www woodward com Woodward has co mpany owned plants subsidiaries and branches as well as authorized dis...

Reviews: