Woodward 3171A Product Manual Download Page 6

EM35MR1/3171A Gas Valve 

Manual 26731 

 

 

 

iv 

Woodward 

 

Electrostatic Discharge Awareness 

 

 

 

Electrostatic 

Precautions

 

Electronic controls contain static-sensitive parts. Observe the 
following precautions to prevent damage to these parts: 

 

Discharge body static before handling the control (with power to 
the control turned off, contact a grounded surface and maintain 
contact while handling the control). 

 

Avoid all plastic, vinyl, and Styrofoam (except antistatic versions) 
around printed circuit boards. 

 

Do not touch the components or conductors on a printed circuit 
board with your hands or with conductive devices. 

To prevent damage to electronic components caused by improper 
handling, read and observe the precautions in Woodward manual 

82715

Guide for Handling and Protection of Electronic Controls, 

Printed Circuit Boards, and Modules

 
Follow these precautions when working with or near the control. 
1. 

Avoid the build-up of static electricity on your body by not wearing clothing 
made of synthetic materials. Wear cotton or cotton-blend materials as much 
as possible because these do not store static electric charges as much as 
synthetics. 

2. 

Do not remove the printed circuit board (PCB) from the control cabinet 
unless absolutely necessary. If you must remove the PCB from the control 
cabinet, follow these precautions: 

 

 

Do not touch any part of the PCB except the edges. 

 

 

Do not touch the electrical conductors, the connectors, or the 
components with conductive devices or with your hands. 

 

 

When replacing a PCB, keep the new PCB in the plastic antistatic 
protective bag it comes in until you are ready to install it. Immediately 
after removing the old PCB from the control cabinet, place it in the 
antistatic protective bag. 

 

 

Summary of Contents for 3171A

Page 1: ...Product Manual 26731 Revision D 5 2017 Original Instructions EM35MR1 3171A Gas Valve Installation and Operation Manual...

Page 2: ...amage to the equipment Any such unauthorized modifications i constitute misuse and or negligence within the meaning of the product warranty thereby excluding warranty coverage for any resulting damage...

Page 3: ...4 ACTUATOR VALVE CALIBRATION 15 EM35MR1 Actuator 3171 Gas Valve with Driver 15 CHAPTER 5 TROUBLESHOOTING 16 General 16 Procedure for EM35 Actuator Field Replacement 16 CHAPTER 6 VALVE SIZING NON DLE...

Page 4: ...5MR1 Actuator 3171A Gas Valve Position Switch Resolver 10 Figure 2 4 DVP Driver Drawing 11 Figure 2 5 Plant Wiring Diagram 12 Figure 3 1 Conduit Plug M25 Shown Warning Label 14 Table 6 1 Effective Are...

Page 5: ...verspeed shutdown device to protect against runaway or damage to the prime mover with possible personal injury loss of life or property damage The overspeed shutdown device must be totally independent...

Page 6: ...nd Protection of Electronic Controls Printed Circuit Boards and Modules Follow these precautions when working with or near the control 1 Avoid the build up of static electricity on your body by not we...

Page 7: ...to Pressure Equipment Directive 2014 68 EU on the harmonisation of the laws of the Member States concerning pressure equipment ATEX Valve Exempt from the non electrical portion of the ATEX Directive 2...

Page 8: ...0039 inch Actuator Adaptor Plate to Housing Per drawing 9989 4011 The max gap permitted on this flat joint is 0 099 mm 0 0039 inch Resolver Cover to Housing Per drawing 9989 4013 The max gap permitted...

Page 9: ...ns are intended to alert equipment operators of a potentially unsafe condition and to protect against personal injury loss of life or property damage Valve position error alarm and shutdown thresholds...

Page 10: ......

Page 11: ...eakage and to self clean the metering port Metering port area is determined by input shaft positioning from the actuator The valve has an internal spring to return the valve to the minimum fuel positi...

Page 12: ...y the motor to the cast explosion proof housing and out to the ambient environment Wiring to the motor is accomplished through two 0 750 14 NPT conduit connections or two M25 x 1 5 conduit connections...

Page 13: ...n or around the 3171 Gas Valve assembly The surface of this product can become hot enough or cold enough to be a hazard Use protective gear for product handling in these circumstances Temperature rati...

Page 14: ...oard drain gas volume increases as temperatures drop below 0 C 32 F Plan the vent system taking temperature affects into consideration It is recommended that the end of the drain line outside the encl...

Page 15: ...osphere Conduit seals are required Refer to the Special Conditions for Safe Use stated on page v EXPLOSION HAZARD For Zone 1 Division 1 products Proper torque is very important to ensure that the unit...

Page 16: ...t of the 10 pole WAGO terminal block The actuator power wires should go through the other wiring connection The terminal blocks provided for the motor resolver wires and the position resolver are WAGO...

Page 17: ...Manual 26731 EM35MR1 3171A Gas Valve Woodward 7 Figure 2 2a EM35MR1 Actuator 3171A Gas Valve Resolver NPT electrical conduit entries...

Page 18: ...EM35MR1 3171A Gas Valve Manual 26731 8 Woodward Figure 2 2b EM35MR1 Actuator 3171A Gas Valve Resolver NPT electrical conduit entries...

Page 19: ...Manual 26731 EM35MR1 3171A Gas Valve Woodward 9 Figure 2 3a EM35MR1 Actuator 3171A Gas Valve Position Switch Resolver metric electrical conduit entries...

Page 20: ...EM35MR1 3171A Gas Valve Manual 26731 10 Woodward Figure 2 3b EM35MR1 Actuator 3171A Gas Valve Position Switch Resolver metric electrical conduit entries...

Page 21: ...Manual 26731 EM35MR1 3171A Gas Valve Woodward 11 Figure 2 4 DVP Driver Drawing...

Page 22: ...EM35MR1 3171A Gas Valve Manual 26731 12 Woodward Figure 2 5 Plant Wiring Diagram...

Page 23: ...d geartrains and results in precise position control Having the feedback on the valve also allows for the motor to be repaired or replaced in the field without any loss of calibration The entire motor...

Page 24: ...ly should be properly protected from this water spray 2 Conduit Fittings Woodward recommends that rigid or flexible conduit be used to route the actuator wiring Woodward also recommends that water tig...

Page 25: ...entification serial number and date code must match the valve identification For DLE systems significant turbine damage high emissions levels release of high temperature gas fire damage to nearby equi...

Page 26: ...ault information Overcurrent trips experienced by the driver can be caused by driving the valve into or operating too close to the mechanical stops These stop screws are used for calibration purposes...

Page 27: ...n be viewed through the long vertical slot in the adapter housing 2 Using the 3 16 ball hex driver loosen the socket head cap screw that clamps the coupling assembly to the EM35 output shaft Do not lo...

Page 28: ...en everything is in position first slip the actuator shaft into the coupling assembly then line up the pins of the actuator with the adjacent holes in the adapter housing The actuator should mate up w...

Page 29: ...he gas 1 300 typical for standard natural gas at 60 F Sg Specific gravity relative to air for the gas 0 60 typical for standard natural gas Flow Valve metered flow lb h T Temperature of the gas Deg Ra...

Page 30: ...list the valve effective area for pressure ratios P2 P1 from 0 05 to 0 95 respectively To pick the proper size valve for an application move to the sheet that has a value for effective area greater t...

Page 31: ...nd Application Program The algorithm used for sizing and demand value determination used in the standard valve application programs available for the 3171A is basically the same as that described abov...

Page 32: ...Table 6 1 Effective Area Table 0 45 port Valve angle Resolver Feedback Angle Resolve Offset Angle Resolver Offset Angle 20 degrees 4 mA 0 valve angle 0 valve position 20 resolver angle min stop 2 deg...

Page 33: ...Table 6 2 Effective Area Table 0 56 port Valve angle Resolver Feedback Angle Resolve Offset Angle Resolver Offset Angle 20 degrees 4 mA 0 valve angle 0 valve position 20 resolver angle min stop 2 deg...

Page 34: ...Table 6 3 Effective Area Table 0 80 port Valve angle Resolver Feedback Angle Resolve Offset Angle Resolver Offset Angle 20 degrees 4 mA 0 valve angle 0 valve position 20 resolver angle min stop 2 deg...

Page 35: ...ntenance schedule Each site must determine the appropriate schedule based on the severity of the service conditions Inspect for dirt grease dust or other buildup in the areas of moving parts or joints...

Page 36: ...documentation for details Woodward Business Partner Support Woodward works with and supports a global network of independent business partners whose mission is to serve the users of Woodward controls...

Page 37: ...Distributor Charges for the Replacement Exchange service are based on a flat rate plus shipping expenses You are invoiced the flat rate replacement exchange charge plus a core charge at the time the...

Page 38: ...nical Support Product Training Field Service Technical Support is available from your equipment system supplier your local Full Service Distributor or from many of Woodward s worldwide locations depen...

Page 39: ...213 2191 Korea 82 51 636 7080 The Netherlands 31 23 5661111 Poland 48 12 295 13 00 United States 1 970 482 5811 You can also locate your nearest Woodward distributor or service facility on our websit...

Page 40: ...natural gas Gas pressure 0 to 6205 kPa 0 to 900 psia Electrical Motor Voltage 28 Vdc nominal 18 32 Vdc operating Motor Current 15 A continuous 37 A peak current for 50 ms System Accuracy Using 485 or...

Page 41: ...ated Declarations Changes in Revision C Added DVP Driver drawing Figure 2 4 Changes in Revision B Added Effective Area tables for 0 45 0 56 and 0 80 ports at the end of Chapter 6 Changes in Revision A...

Page 42: ...EM35MR1 3171A Gas Valve Manual 26731 32 Woodward Declarations...

Page 43: ...Manual 26731 EM35MR1 3171A Gas Valve Woodward 33...

Page 44: ...EM35MR1 3171A Gas Valve Manual 26731 34 Woodward...

Page 45: ...Manual 26731 EM35MR1 3171A Gas Valve Woodward 35...

Page 46: ...EM35MR1 3171A Gas Valve Manual 26731 36 Woodward...

Page 47: ...O 80522 1519 USA 1041 Woodward Way Fort Collins CO 80524 USA Phone 1 970 482 5811 Email and Website www woodward com Woodward has company owned plants subsidiaries and branches as well as authorized d...

Reviews: