VENT INSTALLATION
VENT REQUIREMENTS
• Do not crimp or rupture liner when bending it into
chimney offsets.
W
ARNING
•
Vent must meet all vent manufacturer’s requirements when installed.
•
Make sure you have the following before installing unit:
ALTITUDE CONSIDERATIONS
Exhaust
Inlet
Maximum Height
40' (12.9 M)
Minimum Height
10' (3 M)
Maximum
1' (305mm)
Offset
Exhaust
(centered on unit)
Inlet
3" UL
1777 Gas Liner
Termination Kit
Secure with two (2) screws.
Failure to adjust air shutter properly may lead to
improper combustion which can create a safety
hazard. Consult your dealer or installer if you
suspect an improperly adjusted air shutter
W
ARNING
• Make sure the exhaust pipe on heater connects
to exhaust portion of cap. Attach flex liners. See
Figure
6
.
Figure
5
- Venting Unit
Figure
6
- Connecting Exhaust Pipe to Heater
12
This heater has been tested at altitudes ranging from sea level
up
to 4,500 feet
(
Canada
), 0-2000 feet (
USA
). In this testing, heater with standard orifice burns
correctly with just an air shutter adjustment. If you need to resize orifice for
use at high altitude, contact your
Woodbridge Fireplace
dealer.
• 3" UL 1777 Listed gas liner for air inlet and exhaust
(Q-ty: 2 pcs).
• V
ertical termination kit
Duravent, Metal-Fab, or SelKirk.