WOLF
ATEX
LED INSPECTION
LEADLAMP
WOLF
ATEX
LED INSPECTION
LEADLAMP
OPERATION AND MAINTENANCE
INSTRUCTIONS
ATEX and IECEx Certified
for Explosive Atmospheres
•
Ideal for handheld inspection and work
activities in a hazardous area
•
ATEX and IECEx approved for Zone 1
and 21 explosive gas and dust atmospheres.
•
High power ‘fitted for life’ LED light source
•
High quality, even, ultra-wide angle LED light,
reduces shadows and enhances visibility
•
Large diffuse light source minimises eye
discomfort when viewed directly
•
Compact for handheld use
•
Flexible integrated hook for suspension in the
work area
•
Robust and highly durable enclosure to
withstand heavy industrial use
•
Certified to wide voltage ranges
•
Fitted with 10m HOFR cable as standard
•
IP67 rated for use in the harshest environments
•
Group I mining approval
•
Mounting and protection accessories available
WOLF SAFETY LAMP COMPANY
Saxon Road Works, Sheffield,
S8 0YA, England
Tel: +44 114 255 1051
Fax: +44 114 255 7988
Email: [email protected]
Website: www.wolf-safety.co.uk
SP-500 Issue 01
DF345
MMD/??/??.16/??K
CABLE REPLACEMENT
4. Fit the LED module into one half of the enclosure body,
make sure the grommet is seated in the handle section and
fit the other half of the enclosure body making sure the hook
and M8 nut are fitted. Secure the enclosure body assembly
using the three allen head bolts and nuts (do not over-
tighten).
Note:
• Do not dislodge, pull or attempt to remake ends on
wires exiting the potting compound.
• Take care not to trap/crush wires, ensure all seals are
present and in good condition.
3. Tighten the gland onto the cable and replace the back cover
to the LED module.
0.6Nm
SP-600
ELECTRICAL DATA
Model
SP-600H…
SP-600L…
SP-600EL…
AC Voltage
90-264V*
18-54V
9-16V
DC Voltage
N/A
20-54V
9-16V
Current
0.08A
0.6A
0.8A
VA (AC)
6.82
9.12
8.28
*Power factor >0.95
Note: All variants certified safe for voltages down to 0V AC/DC.
Suitable for 50-60Hz AC supplies.
CABLE REPLACEMENT
1
3
2
4
1. Remove the three allen head bolts from the enclosure body,
separate the two halves of the enclosure then remove the
LED module, unscrew the four screws that retain the rear
metal cover to the LED module.
2. Unscrew the cable cores from the two way terminal block
and remove the cable from the gland. Make sure that all
gaskets are retained and fitted correctly upon re-assembly.
Fit the replacement cable through the grommet then the
gland and terminate the inner cores into the terminal block.
Ex terminal
W-463
4
IMPORTANT
No modifications are permitted to the ATEX LED Inspection Leadlamp.
LENS COVER REPLACEMENT
0.6Nm
2.5mm
3mm
2.5mm
0.8Nm
0.85Nm
30mm
Max 8mm
Max 8mm
30mm
Max 8mm
Ensure <1mm conductor
exposed from the metal
of the terminal throat