Installation Instructions
Prior to the application of fastening sets the static conditions of the concrete or
steel bars have to be checked and taken into account.
Assembly exclusively with basic units at a total depth of 300 mm.
Fixing
rail
Suspending
rail
Fastening
brackets
LH-Unit
Suspending rail
Fastening bracket
- Fasten fixing rail with dowels and screws, provided on site, to the concrete bar.
- Fit fastening brackets to the unit with enclosed screws.
- Fit suspending rails to the fastening brackets with enclosed screws, washers and nuts.
- Hang total assembly (unit fastening brackets and suspending rails) into fixing rail.
To prevent the unit from dropping before fitting the pipework, the inferior suspending rail
may be secured additionally by fitting it to the concrete bar with screws and dowels.
Fastening kit for concrete bar
vertical
Suitable for all types af steel bars at a flange width "b" of min. 100 mm up to max. 300
mm, and a flange thickness "t" of min. 6 mm up to max. 21 mm.
- Fit fixing rail to steel bar with enclosed clamping jaws.
- Fit fastening brackets to the unit with enclosed screws.
- Fit suspending rails to the fastening brackets with enclosed screws, washers and nuts.
- Hang total assembly (unit, fastening brackets and suspending rails) into fixing rail.
- Fit inferior suspending rail to steel bar with clamping jaws.
Fastening kit for steel bar
vertical
b
t
Fastening bracket
Fixing rail
Clamping jaws
Suspending rail
Fastening bracket
Suspending rail