Wizmart NB338 Series Installation Wiring Diagram Download Page 2

HEAT SENSOR TESTING 

The detector to be tested should be subject to a flow of 
warm air at a temperature of between 65

°

C and 80

°

C. 

(This requirement can be met by some domestic hair 
dryers). 
Proceed as follows: 
1. Switch on the warm airflow and check that temperature 

is correct and stable. 

2. From a distance of several inches, direct the airflow at 

the guard protecting the thermistor. The detector 
should alarm within 30 seconds. 

3. Upon alarm immediately remove the heat source and     

check that the red LED of the detector is illuminated. 
Reset the detector from the control panel. 

4.If detector fails to go into alarm mode within 30 

seconds it is too insensitive and needs to be returned 
to the distributor for servicing. 

5. After testing, check that the system is set for normal 

operation and notify the appropriate authorities that the 
testing operation is complete and the system is active 
again. 

NOT SUITABLE FOR INSTALLATION IN AREAS 
WHERE AIR VELOCITIES EXCEED 300 ft/min 

MAINTENANCE 

The recommended minimum requirement for detector 
maintenance consists of an annual cleaning of dust from 
the detector head by using a vacuum cleaner cleaning 
program should be agreed to the individual environment 
in conformance with NFPA-72A standard. 
 

CAUTION: DO NOT ATTEMPT TO DISASSEMBLY OF THE 
FACTORY SEALED SMOKE DETECTOR. THIS 
ASSEMBLY IS SEALED FOR YOUR PROTECTION AND IS 
NOT INTENDED TO BE OPENED FOR SERVICING BY 
USERS. OPENING THE DETECTOR HEAD WILL VOID 
THE WARRANTY. 
 
REFERENCE TO THE TECHNICAL BULLETIN ISSUE NO. 
NBTB20031106,REV.A 

 

SPECIFICATION 

Model 2/4 

 

wire 

Ther

mal 

Voltage 

DC 

Standby 

Current 

(Max.) 

Alarm 

Current 

(Max.) 

Surge

Current

(Max.)

Star-Up 

Time 

(Max.) 

Permissible

Current 

(Max.) 

Frequency

Alarm  

Sound level

Alarm contact 

Base model 

NB338-2 2 

 

28/12V 

90

μ

70mA 

120

μ

A

60 Seconds

80mA 

3-5 Seconds

 

P/N772912 

NB338-2L  

 

28/12V 

90

μ

70mA 

120

μ

A

60 Seconds

80mA 

3-5 Seconds

 

P/N774912 

NB338-4-12 4 

 

12V 

320

μ

35mA 

120

μ

A

60 Seconds

80mA 

3-5 Seconds

Form A 

P/N774912 

NB338-4-24 4 

 

24V 

320

μ

35mA 

120

μ

A

60 Seconds

80mA 

3-5 Seconds

Form A 

P/N774912 

NB338-2H 2 

57

°

C 28/12V  100

μ

70mA 

130

μ

A

60 Seconds

80mA 

3-5 Seconds

 

P/N772912 

NB338-2HL  

57

°

C 28/12V  100

μ

70mA 

130

μ

A

60 Seconds

80mA 

3-5 Seconds

 

P/N774912 

NB338-4H-12  

57

°

C 12V  320

μ

35mA 

130

μ

A

60 Seconds

80mA 

3-5 Seconds

Form A 

P/N774912 

NB338-4H-24  

57

°

C 24V  320

μ

35mA 

130

μ

A

60 Seconds

80mA 

3-5 Seconds

Form A 

P/N774912 

 

Remarks:

 

H

-heat/ 

L

-remote LED indicator output 

 

LIMITED WARRANTY STATEMENT 

WIZMART TECHNOLOGY, Inc. represents that this product is free from defects in material and workmanship. And it will 
repair or replace any product or part thereof which proves to be defective in workmanship or material for a period of twelve 
(12) months from the date of purchase but not to exceed eighteen (18) months after shipment by the manufacturer. For a full 
description of WIZMART TECHNOLOGY

S LIMITED WARRANTY, which, among other things, limits the duration of 

warranties of merchantability and fitness for a particular purpose and excludes liability for consequential damages. Please 
read the entire LIMITED WARRANTY on the WIZMART quotation. Acceptance of order and/or original invoice which will 
become part of your sales agreement. Please contact WIZMART TECHNOLOGY directly for a return merchandise 
authorization (RMA) number before returning goods to the factory. Shipment must be prepaid and WIZMART will repair or 
replace your returned detector. 

 

 