![WIPCOOL R4 Operation Manual Download Page 3](http://html.mh-extra.com/html/wipcool/r4/r4_operation-manual_988380003.webp)
03
04
feeling for more
feeling for more
3.2 Operating Instruction
3.2.1 Check Before Operation
(Only qualified service personal should operate this unit , may require the user to be
licensed for some countries )
■
Working-spot should have good lighting and Atmospheric conditions.
■
Make sure the charging refrigerant oil from the oil tank is the same as the type
indicated on the nameplate.
■
Make sure with the correct voltage as the same as nameplate.
3.2.2 Oil Charging Process
3) Open the oil charging valve , switch on the oil pump to start to charge the oil.
4) Running the compressor to review if the oil level . pressure . oil temperature is under
normally conditions, and do the adjustment if necessary.
5) Remove the oil tank .oil pump and outlet hose if everything is fine, wipe out the rest
oil inside hose and pump. Pack them with sealed plastic bag ,then keep the
compressor running again.
R4
R6
1.5m
Outlet tube
1/4"SAE
3/8"SAE
Portable
Toolbox
1.5m
Outlet tube
1/4"SAE
3/8"SAE
Portable
Toolbox
3.1.3 Accessories
3.1.4 Product Indication Chart
Pressure Gauge
Pressure
Relief Valve
Oil Return Tube
Oil Inlet Pipe
Non-slip Handle
Motor
Shockproof Stand
Pump Head
Non-slip Handle
Motor
Shockproof Stand
Pump Head
Oil Outlet
Oil Return Valve
Oil Inlet
1) Clean the inlet and outlet hose to protect the oil mix,connect to the oil pump,then
insert the inlet hose to the tank.
2) Switch on the pump for suction oil and discharge the air from the inlet hose and
pump body,then switch off the pump once make sure no air inside
(
Judgment
Principle: The discharged oil has no foam or obvious air discharge noise, proves that
the air has been discharged ). Connect the outlet hose to the oil charging valve of
compressor.
3) Open the oil charging valve , switch on the oil pump to start to charge the oil.
4) Running the compressor to review if the oil level . pressure . oil temperature is under
normally conditions, and do the adjustment if necessary.
5) Remove the oil tank .oil pump and outlet hose if everything is fine, wipe out the rest
oil inside hose and pump. Pack them with sealed plastic bag ,then keep the
compressor running again.