Troubleshooting
5-17
Problem: The following errors indicate failures on the WPC 2000 Main Processor board or
the DSV/Lockout Relay board. Error codes F70, F71, F72/H72, F73/H73, and
F76/H76 indicate failures with the DSV driver logic on the Main Processor board.
Codes F74/H74, F75/H75, and F77 indicate failures with the relays on the DSV/
Lockout Relay board. F78 indicates an issue with the poppet position sensors in
the DSV valve itself.
Remedy:
Press Reset/Select. If the error persists, contact Wintriss Tech. Support for
assistance or replacement of either board.
Loss of Rotation
Problem: The Dual Safety Valve (DSV) has been activated, but the resolver did not start
rotating within the Start-time Limit set on the WPC 2000.
The Start-time Limit setting may be too short. Alternatively, the drive belt on the
resolver may be loose or broken, and the resolver may not be turning continuously
with the press crankshaft, or have stopped turning altogether. Also, the resolver
may be defective.
Air pressure to the clutch may be low, or the clutch may be bad, resulting in no
movement of the crankshaft (and resolver) even though the DSV is energized. In
addition, an internal WPC 2000 problem could have occurred.
Remedy:
Check the Start-time Limit setting, and re-initialize if necessary (see Initializing
Only the Start-time Limit, page 3-5). Check the resolver and resolver drive, and
replace the resolver if necessary. Check the clutch and repair if necessary. If these
solutions do not work, contact Wintriss Tech. Support.
F70
DSV relay driver A was not off at start of stroke
F71
DSV relay drivers A and B did not turn on properly or have shorted
F72 or H72 DSV Control Flip-flop is not functioning properly
F73 or H73 DSV Missing Pulse Detector window is not functioning properly
F74 or H74 DSV relay A or B did not close properly at start of stroke
F75 or H75 DSV relay A or B did not open properly at end of stroke
F76 or H76 Lockout relay driver did not turn on properly during testing
F77
Lockout relay check contacts were not closed before lockout relay
was turned on
F78
The position of the DSV poppets is incorrect (Minster version only).
F79
Summary of Contents for wpc 2000
Page 91: ...1128500 WPC 2000 User Manual 2 64 Installation ...
Page 191: ...1128500 WPC 2000 User Manual 5 22 Troubleshooting ...
Page 209: ...1128500 WPC 2000 User Manual A 18 Extracts from OSHA and ANSI ...
Page 225: ...1128500 WPC 2000 User Manual G 6 Glossary ...
Page 231: ......
Page 232: ......
Page 233: ......
Page 234: ......
Page 235: ......
Page 236: ......
Page 237: ......
Page 238: ......
Page 239: ......
Page 240: ......
Page 241: ......
Page 242: ......
Page 243: ......
Page 244: ......
Page 245: ......
Page 246: ......
Page 247: ......
Page 248: ......
Page 249: ......
Page 250: ......