WPC 2000 User Manual
1128500
Initialization, Setup, and Checkout
3-29
Switch 5 – Prior Act Time for Automatic Stroke Modes
Switch 5 controls the Prior Act time for Automatic Single-stroke and Automatic Continuous
On-demand operating modes if one or both of these options have been installed on your press
(see Table 3-8). The Prior Act time is the interval within which the activating signal from the
feed device or robot must be received in order to initiate a stroke.
When switch 5 is set to OFF, its default setting, the activating signal must be received within a
30-second window for Automatic Single-stroke and a 1-minute window for Automatic
Continuous On-demand. When switch 5 is set to ON, the window increases to 5 minutes for
Automatic Single-stroke and 10 minutes for Automatic Continuous On-demand.
Wiring instructions for Automatic Single-stroke are provided on page 2-48. Operating
instructions for Automatic Single-stroke are provided on page 4-16. For information on
wiring and operating Automatic Continuous On-demand, call Wintriss Tech. Support.
Switch 6 – Enabling Dual Light Curtains
Switch 6 controls whether WPC 2000 recognizes dual light curtains when two light curtains
are wired to the system, as shown in Table 3-9. Refer to page 2-18 for general light curtain
installation instructions.
When switch 6 is set to OFF, its default position, dual light curtains are disabled, and WPC
2000 recognizes only a single light curtain. When switch 6 is set to ON, dual light curtains are
enabled, and both light curtains, if two light curtains are wired, are recognized.
Switch 7 – Disabling Access to Stop-time Limit and Auto Carry-up Angle
Settings
Switch 7 controls access to Stop-time Limit and Auto Carry-up Angle settings, as shown in
Table 3-10, page 3-30.
When set to OFF, the default setting, switch 7 enables changes to be made to the current
Stop-time Limit and Auto Carry-up Angle values stored in WPC 2000. Setting switch 7 to
ON disables this feature, preventing the operator from making changes.
Table 3-8. Switch 5 Settings (S101): Prior Act Times for Automatic Modes
Setting
Prior Act Time
Automatic Single-stroke
Prior Act Time
Automatic Continuous On-demand
OFF
30 seconds (Default)
1 minute (Default)
ON
5 minute
10 minutes
Table 3-9. Switch 6 Settings (S101): Enabling Cam Adjustments
Setting
Dual Light Curtains
OFF
Normal operation (Default). Dual light curtains disabled.
WPC 2000 recognizes only one light curtain.
ON
Dual light curtains enabled. WPC 2000 recognizes two
light curtains.
Summary of Contents for wpc 2000
Page 91: ...1128500 WPC 2000 User Manual 2 64 Installation ...
Page 191: ...1128500 WPC 2000 User Manual 5 22 Troubleshooting ...
Page 209: ...1128500 WPC 2000 User Manual A 18 Extracts from OSHA and ANSI ...
Page 225: ...1128500 WPC 2000 User Manual G 6 Glossary ...
Page 231: ......
Page 232: ......
Page 233: ......
Page 234: ......
Page 235: ......
Page 236: ......
Page 237: ......
Page 238: ......
Page 239: ......
Page 240: ......
Page 241: ......
Page 242: ......
Page 243: ......
Page 244: ......
Page 245: ......
Page 246: ......
Page 247: ......
Page 248: ......
Page 249: ......
Page 250: ......