sed from 180⁰ to 210⁰. Actuations Within That Window Are
Ignored.
A Bypass Angle can be added on the sensor program screen, Figure 6-11. The default setting is for no
bypass angle. If a bypass angle is required, press ADD to program a bypass window. To remove a
previously programmed bypass, press CLEAR BYPASS on the bypass angle programming screen,
Figure 6-12. This will remove the bypass window and return the “ADD” button on the sensor
programming summary screen.
MINIMUM ACTUATION TIME (Static Sensors)
The Bypass Angle is effective when you know the approximate angle during which a nuisance fault
can occur. For applications that experience nuisance faults on static sensors at random times during
the stroke, use the Minimum Actuation Time setting. This feature enables the DiProPAC to ignore
short actuations of static sensors but will stop the press when a fault persists for longer than the
specified minimum actuation time. The value can be set from 10 to 2500 ms. The default value is 0,
which turns this feature off.
Set the Minimum Actuation Time in the Sensor Program screen, Figure 6-11.
1.
Press the MIN ACTUATION item. A numeric entry window appears
2.
Key in the minimum actuation time.
3.
Press enter. The Sensor Program screen shows the value you entered.
Cyclic Sensors: Green Sensors
Green sensors monitor cyclic events that must occur during a certain portion of each stroke or
intermittently every designated number of strokes. Examples are part ejection, stock feed, and part
transfer.
SmartPAC PRO stops the press if a green sensor fails to actuate during its Ready Signal, or if it
actuates at the wrong time.
Summary of Contents for SmartPAC PRO
Page 1: ......
Page 2: ......
Page 4: ......
Page 6: ......
Page 20: ......
Page 22: ......
Page 24: ......
Page 42: ...1143100 SmartPAC PRO User Manual 42 Chapter 1 Introduction to SmartPAC PRO ...
Page 142: ...1143100 SmartPAC PRO User Manual 142 Chapter 4 SmartPAC PRO Program Mode ...
Page 200: ...1143100 SmartPAC PRO User Manual 200 Chapter 6 Using DiProPAC Die Protection Optional ...
Page 222: ...1143100 SmartPAC PRO User Manual 222 Chapter 7 ProCamPAC Instructions ...
Page 254: ...1143100 SmartPAC PRO User Manual Appendix C SmartView Remote Viewing and E mail Setup 254 ...
Page 280: ...SmartPAC PRO User Manual 1143100 280 Appendix C Reporting Downtime and Scrap to SFC ...
Page 290: ...SmartPAC PRO User Manual 1143100 290 Index Y yellow fault 232 yellow sensor 169 ...
Page 292: ......
Page 294: ......
Page 296: ......
Page 298: ......
Page 300: ......
Page 301: ......
Page 302: ......
Page 303: ......
Page 304: ......
Page 305: ......
Page 306: ......
Page 307: ......
Page 308: ......
Page 309: ......
Page 310: ......
Page 311: ......
Page 312: ......
Page 313: ......
Page 314: ......
Page 315: ......
Page 316: ......
Page 317: ......
Page 318: ......