8 Z
ONE
W
ATER
B
UG
Model: WB-800
Installation/Operation
Instructions
D-011-0008 Rev E (Sep 2009)
D
ETECT
W
ATER
B
EFORE
A
DVERSE
C
ONDITIONS
A
RISE
S
YSTEM
O
VERVIEW
The WB800 is a completely electronic water detector which is designed to detect only
nonflammable conductive liquids (distilled water cannot be detected). The WB800 is
designed with the control console mounted on the wall and the remote sensors placed in
locations where water seepage is most probable.
The unit includes four (4) supervised sensors (PN W-S-S). In addition to detecting water with
this sensor, an the unit will alarm when the supervised sensor line becomes disconnected.
A film of moisture forming a bridge between the two metallic contacts on any remote
sensor is all that is needed for the unit to signal an alarm condition (Figure 1). The relay
output is non-latching, but will remain closed until the moisture bridge between the two
contacts is broken. As sensitive as the WaterBug is, it will not alarm due to high humidity
or condensation. The WaterBug is ideal for use around homes, office buildings, computer
rooms, boats, etc. Additional features include:
• Accepts 12V, 24V AC/DC power input
• Eight alarm LED indicators to identify the sensor zone in alarm.
• Supervised sensor line option. Unit will alarm on open sensor condition and an
indicator will light. Up to 8 supervised sensors per console. Sensor lines up to 500ft.
• One “Form C” SPDT Relay for alarm output.
• Built in audible alarm and remote buzzer output with silence feature (adjustable 3 sec.
to 150 min.)
M
OUNTING
C
ONSIDERATIONS
Select A Site For The Console
Sensor cable lengths & power source locations should be considered. Maximum cable
length for the water sensors is 500 ft.
Option #1 Surface Mounting Without Mounting Box
It is possible to install the console on a soft wall (sheet rock, panel, etc.) without the
use of a mounting box. This is the fastest mounting method and it gives the control
console a nice looking low profile. In selecting a site to mount the console keep in
mind that it must be placed in a secure, dry location with an ambient temperature
of +32˚ to +130˚F (0˚ to +54˚C). For this option, drill a ½” diameter hole(s) in the wall
which will be opposite the wiring terminal strip on the console. This hole will provide
access for all wiring. Next, carefully mark the location of the four corner screw holes on
the console. Then drive four wall anchors into the proper locations and complete by
attaching the console to the wall.
Option # 2 Surface Mounting
In areas where no hollow interior walls are available, the surface mounting box (PN
MB-3M) can be used. The surface mounting box (3 gang electric box) can be secured to
any wall. The installed profile of the WB800 with this option is about 2½“ out from the
wall.
S
PECIFICATIONS
Dimensions
6.55” X 4.7” X1.0”
(166 cm X 119 cm X 25cm)
Weight
1 lb (0.45kg)
Mounting
Can be flush mounted directly to the
wall or mounted to a 2348-3 Wiremold
surface mount box (PN MB-3M)
Input Voltage
12 VDC/24 VDC ≤ 100 mA
(including alarm conditions)
12VAC/24VAC RMS ≤ = 200 ms
Max number of sensors
8 (1 per zone, supervised mode)
16 (2 per zone, unsupervised mode)
Console Temp. Range
+32˚ to +130˚F (0˚ to +54˚C)
Sensor Temp. Range
+32˚ to +130˚F (0˚ to +54˚C)
Alarm Relay Output (1)
SPDT Relays (1 Amp @ 30 VDC/AC)
Remote Buzzer Output
Current Draw- 25 mA (Max.)
Warranty
1 Year Limited
O
NE
Y
EAR
L
IMITED
W
ARRANTY
Winland Electronics, Inc. warrants that each product of its manufacture is free from defects in material and factory workmanship, when
properly installed and operated under normal conditions according to the manufacturer’s instructions.
Manufacturer’s obligation under this warranty is limited to correcting, without charge, at its factory any part of parts thereof which shall
be returned to the factory, by the original retail purchaser, transportation charges prepaid, within one year after purchase and which upon
examination shall disclose to the manufacturer’s satisfaction to have been originally defective. Correction of such defects by repair to, or
supplying of replacements for defective parts shall constitute fulfillment of all obligations to purchaser. Repair service performed by the
manufacturer after one year from date of purchase will be for a reasonable service charge.
This warranty shall not apply to any of the manufacturer’s products which have been subject to misuse, negligence or accident of which
shall have been repaired or altered outside of the manufacturer’s factory.
Manufacturer shall not be liable for loss, damage, or expense directly or indirectly from the use of its product or from any other cause.
THIS WARRANTY IS IN LIEU OF ALL OTHER WARRANTIES, EXPRESSED OR IMPLIED. WARRANTIES OF MERCHANTABILITY AND FITNESS FOR
PARTICULAR PURPOSE ARE EXCLUDED, AS ARE ALL OTHER REPRESENTATIONS TO THE USER-PURCHASER, AND ALL OTHER OBLIGATIONS
OR LIABILITIES, INCLUDING LIABILITY FOR INCIDENTAL AND CONSEQUENTIAL DAMAGES, ON THE PART OF THE MANUFACTURER OR THE
SELLER.
No person, agent or dealer is authorized to give any warranties on behalf of the manufacturer nor to assume for the manufacturer any
other liability in connection with any of its products.
A
DDITIONAL
W
ATER
D
ETECTION
P
RODUCTS
:
WaterBug 200
Run as many as 6 sensor probes up to 100’ away
Hardwire powered
Includes one standard unsupervised sensor
WaterBug 350
Run as many as 6 sensor probes up to 100’ away
9V battery powered with low battery alarm and integrated buzzer
Includes one standard unsupervised sensor
EnviroAlert EA200
Utilize a supervised WaterBug sensor and monitor temp simultaneously
Eight event alarm memory with date and time
Auxiliary output relay for local audible alarm
EnviroAlert EA400
Simultaneously monitor 4 zones for water, temperature, and/or humidity
Eight event alarm memory with date and time
Auxiliary output relay for local audible alarm
EnviroAlert EA800
Simultaneously monitor 8 zones: 4 wireless and 4 hardwired
Complete downloadable data logging via USB stick
Monitor for water, temperature, humidity, contact closure, and more
A
DDITIONAL
S
ENSORS
AND
A
CCESSORIES
W-S-S
WB Sensor Supervised Standard
(Up to 8 per WB800 console)
W-UC-S
WB Undercarpet Supervised Standard Sensor
(Up to 8 per WB800 console)
W-S-U
WB Sensor Unsupervised
(Up to 16 per console)
W-UC-U
WB Undercarpet Unsupervised Sensor
(Up to 16 per console)
MB-3P
Mounting Box 3 Gang (Plastic)
12VDCT
12VDC Wall Mount Power Supply
BZ-1
Optional Remote Announicator
TSW
Additional Temp Sensor Wire
(22 AWG, twisted pair, solid) specify length
Note:
Supervised sensors are recommended for new WB800 installations.
C
ONTENTS
This package contains:
• 1 WaterBug WB800 Console
• 4 Standard Supervised Water Sensors (PN
W-S-S)
• 1 Mounting Box 3 Gang Metal (PN MB-3M)
• 4 Phillips screws for mounting
• 1 Installation/Operating Instructions Guide
A
DDITIONAL
I
NFORMATION
1. The WB800 is included with four (4) standard
supervised sensors (PN W-S-S).
2. A backbox is included with the WB800. If
desired, the other mounting methods as
described in the Installation/Operation
Instruction Guide may be used. Screw
packets are also provided to mount the
backbox to the wall and also to mount the
WB800 console to the backbox. Both a
standard slotted and phillips screwdriver are
necessary for installation.
3. You will need a slotted screwdriver to install
the enclosed backbox. Using the backbox as
a template, mark the position of the screw
holes on the vertical surface you wish to
mount to. Drive the screws (using anchors if
required) in your mounting surface, allowing
approximately 1/16” between the screw head
and the mounting surface. Engage key slots
on the backbox with the screw heads and
press down.
4. After completion of wiring, the enclosed four
phillips screws can be used to mount the