background image

4

5

Position/fitting

The evaporator must be positioned so that it does not blow on the door, as this can cause

condensation in the frame. It is also important that it is positioned so that there is good

air circulation in the room. The stretch of pipe between the compressor and evaporator

must  not  exceed  10  metres.  When  fitting  in  completed  element  rooms  and, the 

pipes  from  the  evaporator  are  pulled  up  through  the  ceiling  and connected together

at the top of the ceiling. The stretch between the pipes must be well insulated.

It is important to avoid long oil pockets in the pipework (straight pipes).

1. Fit the evaporator part in the ceiling/wall with 4 screws 4 x 35 mm. Prepare for 

propriate connection across the ceiling. Remember to have a sufficiently long cable

to the 5 pin plug for quick connection.

2. Wait screwing onto the plastic cover until after vacuuming and filling.

3. Attach the drainage hose. Pull the rubber through the drainage hole.

The  compressor  part  is  fitted  to  the  wall  or  put  on  the  floor  in  a  suitable  place.

Consideration must be made for air coming in and out of the unit. Do not place the unit

under stairs/enclosed areas etc. where there is minimal air ventilation.

1. The compressor bracket has 4 x rubber mufflers on the bottom.

2. The compressor bracket is placed on a pre-fitted shelf or fixed to the wall with

screws.

3. Secure the unit with the disc and screws through the 2 outer rubber dampers.

(shelf/floor).

4. Suction (8mm) and fluid pipes (6mm) are soldered to the compressor pipe and filter

respectively.

5. The unit is vacuumed and leak tested with a drop test. The ambient temperature

upon vacuuming must be above 15°C. If there is a leak, the unit must be 

pressure-tested and re-vacuumed.

6. 

7.  Connect  the  wires  to  the  right  colours  according  to  the  drawing  for  5-pin  fast

connection, and position in respective connections. Normal suction pressure during

operation is between 10-15°C.

The evaporator part without fitted cover must run over upon correct filling. Check the

thermostat stops the compressor by switching the thermostat to the far right and into

OFF mode. Re-fit cover, and drainage hose. Put a box or towel over the entire 

evaporator box for faster check of correct filling, and in/out connection on thermostat.

For correct suction pressure it is also important that the cover on the compressor unit

is fitted.

Set the thermostat to 1o'clock. After 1-2 days, adjust to the right temperature.

4

Use and maintenance

Setting the temperature:

DEFROSTING TIMER: TL10 and TL16 have a defrosting timer and must be supplied

from the factory with defrosting of 4x15 min. per 24 hours. The defrosting timer is

adjusted according to requirements in each case. 1 turn outwards is 15 mins. 

defrosting.

CLEANING: The compressor unit has a dust filter at the front, which can be pulled out

and should be vacuumed 4 times a year as required. Remember to unplug before 

cleaning. When cleaning the evaporator cover and inside the fridge, use mild soapy 

water with a small amount of chlorine to prevent mould forming. Draining of 

condensation water should be checked regularly including that the water runs free to 

the containeror the drain.

5

Simple problem solving

Fault

Reason

Need

Poor refrigeration

Dust filter

Clean filter

Fan motor on warm side defect

Order new fan

Ambient temperature too high 

Improve ventilation

Fan motor on cold side defect  Order new fan

Evaporator full of ice 

Manual defrosting

No refrigeration 

Compression not running 

Check fuse/plug

Compressor not working 

Call + 47 69102402

Water running over

Drain 

Open drain

The thermostat has a working area of 5 - 15 degrees Celcius.  When the 

thermostat knob is turned clockwise, the temperature is reduced and the cellar 

gets colder.  Counter clockwise warmer.  The correct temperature for wine is set 

with a thermometer in a glass of water 12/13 degrees is the ideal temperature for 

most wine.

With a temperature of 13 degrees the air temperature will be between 11 and 15 

degrees C in the cellar.

Reviews: