INSTALLATION AND USER MANUAL WINESP40CAPRO
Page 7
2.
EQUIPMENT
The air conditioner is composed of 2 separate units, of a thermostat and a wiring box. They must be
connected by frigorific ducting pipes and electric connections.
The ducting pipes length between both units should not exceed 20m.
2.1.
Outside unit
The unit must be installed outside or in a room.
If the unit is installed outside:
- Place the unit in order the air suction and air rejection are not disturbed
- Encourage the installation in open areas and sheltered from the sun
- Be cautious to the noise to the neighborhood
- Raise the unit to prevent from accumulation of water and snow
If the unit is installed in a room :
- Place the unit in order the air suction and air rejection are not disturbed
- Ensure there is a good ventilation
- Maximum temperature and non permanent≤ 40°C
- Ideal temperature ≈ 20°C.
2.2.
Inside unit
Install the inside unit only inside the cellar.
2.3.
Thermostat
The thermostat can be installed either inside or outside the cellar.
If installed outside, take into consideration the length of the temperature probe to be installed into the
cellar.
The delivered probe has a length of 1.5m. It can be extended by flexible cable isolated to 2 drivers of
minimal section of 0.5mm2.
2.4.
Connection box
The connection box can be installed too either inside or outside the cellar.
If installed outside, take into consideration the cable length ( 2 m)
2.5.
Connection drawing
TAKE INTO CONSIDERATION THE CABLE LENGTHS BETWEEN THE
CONNECTION BOX AND THE UNITS
INSIDE UNIT
CABLE LENGTH 2M
OUTSIDE UNIT
NO CABLE SUPPLIED
THERMOSTAT
CABLE LENGTH 2M
MAIN CONNECTION
NO CABLE SUPPLIED