background image

VertaMax User Manual 

 

Revision 1.1 

 
Actual operating time from a battery will depend upon the current draw from the battery. A battery will deliver 
less total power (energy) as you draw higher amps. A 100 amp-hour battery can deliver 5 amps for 20 hours 
(100 amp-hours) but it will only deliver 50 amps for 1 1/2 hours (50 x 1.5 = 75) or 75 amp-hours at the higher 
rate. 
 
Also remember, battery life is decreased if the battery is discharged fully. Lead acid batteries have the 
longest life, if they are kept fully charged. 

4.4.3 

Battery Capacity 

Select a battery or system of batteries that will provide your Inverter with proper DC voltage and an adequate 
amp-hour capacity to power your application. Even though VertaMax Inverters are highly efficient at DC-to-
AC inversion, their rated output capacities are limited by the total amp-hour capacity of connected batteries 
and the support of charging devices connected to the battery (e.g. a vehicle alternator, solar panel, wind 
turbine, battery charger). 

STEP 1: Determine Total Wattage Required 

 

Add the wattage ratings of all equipment you will connect to your Inverter. Wattage ratings are usually listed 
in equipment manuals or on nameplates. If your equipment is rated in amps, multiply that number times AC 
utility voltage to determine watts. (Example: a 

¼

 in. drill requires 2

½

 amps. 2

½

 amps 

×

 120 volts = 300 

watts.)  

Note: Your Inverter will operate at higher efficiencies when used at about 75% - 80% of the inverter’s rating. 

 

STEP 2: Determine DC Battery Amps Required 

 

Divide the total wattage required (from step 1, above) by the battery voltage (12) to determine the DC amps 
required.  
 

STEP 3: Estimate Battery Amp-Hours Required

 

Multiply the DC amps required (from step 2, above) by the number of hours you estimate you will operate 
your equipment exclusively from battery power before you have to recharge your batteries. Compensate for 
inefficiency and wiring losses by multiplying this number by 1.2. This will give you a rough estimate of how 
many amp-hours of battery power (from one or several batteries) you should connect to your Inverter.  

NOTE: Battery amp-hour ratings are usually given for a 20-hour discharge rate. Actual amp-hour capacities 
are less when batteries are discharged at faster rates. For example, batteries discharged in 55 minutes 
provide only 50% of their listed amp-hour ratings, while batteries discharged in 9 minutes provide as little as 
30% of their amp-hour ratings. 

 

You must allow your batteries to recharge long enough to replace the charge lost during Inverter operation or 
else you will eventually run down your batteries. 
 

5  TROUBLESHOOTING AND SUPPORT 

The VertaMax is ruggedly constructed and requires minimal care. It is recommended to inspect all the 
connections at least two times per year for insulation damage or corrosion and to ensure all connections are 
tight and secure. 

5.1  M

AINTENANCE 

&

 

C

ARE

 

Clean the heat sink and area around the controller of any dirt or debris with a moistened cloth. 
 
Tighten the screws on the DC input terminals. Be sure vents and fans are free of dust or debris. 
 
Inspect any batteries for cracked or bulging cases and corroded terminals. 

5.2  F

USE 

R

EPLACEMENT

 

Warning: Be sure all AC and DC connections are removed and the unit is powered off

 

 

Important:

 Do not attempt to replace the fuses if you are not comfortable with electronic devices.

 

 
Important:

 ESD Precautions must be observed as stated in Section 2.1 

 

Page 12 of 16 

windy

nation

 

 

 

 
 

Summary of Contents for PIN-1500-12

Page 1: ...windynation VertaMax Power Inverter PIN 1500 12 PIN 2500 12 User s Manual...

Page 2: ...Voltage 8 3 4 2 Low Input Voltage 9 3 4 3 Power Overload 9 3 4 4 Over Heating 9 3 4 5 Short Circuit 9 3 4 6 Functional Matrix 9 4 Application 9 4 1 Power Consumption 9 4 2 Typical Power Consumption 1...

Page 3: ...excellent overload protection and capacity to operate different reactive loads The Inverter may be used for many different applications including Solar PV battery systems Wind Turbine battery systems...

Page 4: ...inal 120VAC 120VAC USB Output Voltage 5VDC 5VDC Output Frequency Nominal 60 Hz 60 Hz Output Waveform Modified Sine Wave Modified Sine Wave 1 3 2 Physical Specifications Parameter Value Dimension H x W...

Page 5: ...GFPD The system electrical negative should be bonded through a GFPD to earth ground at one and only one location The grounding point may be located in the solar wind circuit or the battery circuit 2 4...

Page 6: ...the cable must be terminated with a battery terminal that clamps to the post on the battery IMPORTANT If there is an excessive voltage drop and the voltage at the inverter drops below 10 volts the in...

Page 7: ...ome appliances are turned on This feature helps protect both the appliance and the inverter from excessive power draws and surges When the power switch is turned on the VertaMax Soft Start will smooth...

Page 8: ...indicator will work as normal operation and will light when the VertaMax is remotely ON 3 2 USB PORT The USB outlet if equipped will supply 5 volts at 500ma to charge and power cell phones MP3 Players...

Page 9: ...e manual power switch 3 4 4 Over Heating When the inverter exceeds a safe operating temperature due to insufficient ventilation or an increase of ambient temperature the inverter will automatically sh...

Page 10: ...TION Appliance Watts Appliance Watts Stereo 200 Microwave 1000 W 1000 Table Fan 200 AC 5 000 BTU 700 TV VCR 250 Computer 300 Small Refrigerator 350 Hair Dryer 1000 Hand Drill 1 2 600 Coffee Maker 1200...

Page 11: ...e power inverter will also draw a small current less than 600mA when turned off and not operating Therefore it should be disconnected from your battery if it will not be used for more than a day The f...

Page 12: ...EP 3 Estimate Battery Amp Hours Required Multiply the DC amps required from step 2 above by the number of hours you estimate you will operate your equipment exclusively from battery power before you h...

Page 13: ...operates for a short period and then turns off Load is trying to draw too much current Be sure load is less than rated watts of inverter Remove excessive load Turn inverter off and back on to reset Al...

Page 14: ...sole and exclusive remedy and the entire liability of Windy Nation its suppliers and affiliates for breach of the warranty is at Windy Nation s option either i to replace the Product or defective com...