14 

 

 

Standard 

±24V 

actuators 

Examples with 20A power 
consumption 
a) 20 pcs. WMX 826-1  
b) 10 sets of 2 pcs. WMX 826-2  
c) 4 pcs. WMU 885-1 
d) 2 sets of 2 pcs. WMU 885-2 
 
 
 

Connection of variants of standard actuators on motor line X1 

 

 

 

MotorLink

®

 actuators 

Examples with actuators per 
motor line 
Ex. 1: 4 pcs. WMX 823-1  
Ex. 2: 2 pcs. WMX 885-2 
Ex. 3: 3 pcs. WMU 826-3 

 

 

 

 

Allowed actuator combinations on a MotorLink

®

 motor line 

The eight motor lines on the motorline card can each be connected to one of the below shown combinations.  

 
-1 (single): one window with one single window 
actuator. Up to four windows each with one 
single window actuator can be connected 
 
-2 (double): one window with two double window 
actuators. 
 
-3 (triple): one window with three triple window 
actuators. 
 
-4 (quad): one window with four quad window 
actuators. 

 

 

 

 

 

Cable monitoring  

When using actuators with MotorLink

®

, the actuators with MotorLink

®

 are monitored by data communication. 

When the team-size does not match, an error is indicated on the yellow diode. 

 

 

J4

 

Connection for power supply

 

J6

 

Connection to input card WCA 3KI

 

J7

 

Connection to power supply

 

 

 

Summary of Contents for MotorController WCC 310

Page 1: ...K WindowMaster 2016 2017 WindowMaster is a registred trademark used under the license by WindowMaster International A S WindowMaster International A S Skelstedet 13 DK 2950 Vedbæk WCC 310 WCC 320 Standard versions Installation instruction MotorController Version 1711 for firmware from version 1 22 motorline card Save this installation instruction to the end user ...

Page 2: ... Max cable length 24V standard actuators 9 8 1 3 Max cable length actuators with MotorLink 9 9 Cable plan for connection to WCC 310 320 Standard version 11 10 Description of cards and mains connection 12 10 1 WCC connection to mains and power supply units WCA 3P3 WCA 3P5 and WCA 3P6 12 10 2 Motor line card WCA 3M4 and WCA 3M8 13 10 3 Input card WCA 3KI 15 10 4 Power supply card WCA 3P6 17 11 Confi...

Page 3: ...mage to assets The connection of the MotorController is reserved for qualified personnel Disconnect all poles of the MotorController from the supply voltage prior to opening installation or assembling Installation and use according to the national regulations 1 3 Application The MotorController is exclusively designed for the automatic opening and closing of windows flaps or doors Always check tha...

Page 4: ...fieldbus interface for KNX If additional motor lines inputs or fieldbus connection is required a Plus version of the MotorController is necessary Motor groups and motor lines A motor group consists of one or more motor lines and all the motor lines are operated simultaneously All motor lines on the motor cards WCA 3M4 WCA 3M8 can be configured for either a 24V standard actuators or MotorLink actua...

Page 5: ...er consumption of all the connected actuators must not exceed 10A or 20A depending on MotorController size Per motorline Per 10A MotorController Per 20A MotorController 24V Actuators MotorLink Actuators 24V Actuators MotorLink Actuators 4 Motorlines 24V Actuators MotorLink Actuators 8 Motorlines WMS 306 1 10 4 10 10 20 20 WMS 306 2 10 2 10 8 20 16 WMS 306 3 9 3 9 9 18 18 WMS 306 4 8 4 8 8 20 20 WM...

Page 6: ...826 2 10 2 10 8 20 16 WMX 803 804 823 826 3 9 3 9 9 18 18 WMX 803 804 823 826 4 8 4 8 8 20 20 WML 820 825 10 0 10 0 20 0 WML 860 1 10 4 10 10 20 20 WML 860 2 10 2 10 8 20 16 WML 860 3 9 3 9 9 18 18 WML 860 4 8 4 8 8 20 20 WMB 801 802 max 4A connected to WMB WMB 811 812 10 2 10 8 20 16 Do not exceed the total power consumption of the motor line When having two locking actuators per motor line it mu...

Page 7: ...n cable Actuators Other components flexible max 6 mm solide max 10 mm min 0 2mm max 1 5mm Operating conditions 5 C 45 C for indoor installation the MotorController may not be covered Max actuator activation duration duty cycle ED 40 4min per 10min Number of motor lines WCC 310 4 x 10A motor line for 24V standard or MotorLink motors WCC 320 8 x 10A motor line for 24V standard or MotorLink motors Ma...

Page 8: ... are visible and well accessible Do not install behind protruding walls door panels or hidden by the building structure 7 5 Assembly instructions Always have assembly installation repair and maintenance of ventilation systems carried out by qualified personnel trained for this purpose Rules to be adhered to for setting up and installation The following safety relevant rules have to be adhered to w...

Page 9: ...wire in the motor cable for communication Example Max actuator cable length with cable cross section 0 75mm2 and actuator current 2A 2 x 56 x 0 75 2 x 2 21m 8 1 2 Max cable length 24V standard actuators The actuator supply cable must have 2 wires If cable monitoring is requested min 3 2 wires current carrying 1 wire for monitoring 24V standard Actuators Do not use the PE wire green yellow wire cab...

Page 10: ...oss section a Total actuator current I 3 wire 0 75mm 3 wire 1 50 mm 5 wire 1 50 mm 2 wire parallel 3 wire 2 50 mm 5 wire 2 50 mm 2 wire parallel 3 wire 4 00 mm 1A 42m 50m 2A 21m 40m 50m 3A 14m 28m 50m 47m 50m 4A 11m 21m 42m 35m 5A 8m 17m 34m 28m 50m 45m 6A 7m 14m 28m 23m 47m 37m 7A 6m 12m 24m 20m 40m 32m 8A 5m 11m 21m 18m 35m 28m 9A 9m 18m 15m 31m 25m 10A 8m 16m 14m 28m 22m 20A 4m 8m 7m 14m 11m ...

Page 11: ...11 9 Cable plan for connection to WCC 310 320 Standard version Above connection plan shows a WCC 320 MotorController ...

Page 12: ...r 3 2 10 1 WCC connection to mains and power supply units WCA 3P3 WCA 3P5 and WCA 3P6 The MotorController WCC 310 is supplied with a 305W SMPS power supply WCA 3P3 The MotorController WCC 320 is supplied with a 605W SMPS power supply WCA 3P5 The power supply is regardless of size placed in the bottom of the MotorController beneath the motor line and input card An AUX WCA 3P6 to which mains is conn...

Page 13: ...pe the total power consumption of actuators connected to a motor line can max be 10A and the total max power consumption for both motor lines must not exceed 10A or 20A depending on type of MotorController Besides actuators also locking actuators espagnolettes actuators type WMB 801 802 and WMB 811 812 can be connected The power consumption of the locking actuators are not to be included in the 10...

Page 14: ...ard can each be connected to one of the below shown combinations 1 single one window with one single window actuator Up to four windows each with one single window actuator can be connected 2 double one window with two double window actuators 3 triple one window with three triple window actuators 4 quad one window with four quad window actuators Cable monitoring When using actuators with MotorLink...

Page 15: ...3KI and J6 på WCA 3M4 WCA 3M8 S3 X1 X8 For connection of comfort keypads For WCC 310 0410 with only 4 motorlines input X5 X8 have no function With the default values are input Active if the contact resistance is smaller than 2kΩ Inactive if the contact resistance is bigger than 3kΩ Input has pull up current of approx 0 8mA min 0 7mA max 1mA Example comfort keypad connected to input X3 Long push 50...

Page 16: ...e supply voltage Input has pull up approx 1mA min 0 7mA max 1 4mA Connection of wind rain and rain sensors WLA 330 and WLA 331 the settings of the sensors are set on the sensor DIP switch 1 3 on WLA 330 must be set for wind speed tolerances Please refer to the installation instruction for WLA 330 for DIP switch settings If no wind rain or rain sensor is connected to S3X9 a 10kΩ resistor must be co...

Page 17: ...he motor line card blinks after a configuration an error has occurred in the configuration see chaptor Fault detection via LED for identification of errors Actuators are to be connected on the motor lines 24V standard actuators and actuators with MotorLink can be connected to all motor lines but a motor line can only be connected to one type of actuators either 24V standard or MotorLink actuators ...

Page 18: ...cated by the diodes yellow diode is lit 14 Commissioning and test run In case of hardware error please see chapter 13 Hardware error To configure the MotorController press and on the input card at the same time for 10 seconds see chapter 11 We recommend that the software of the MotorController is updated the annual maintenance check 14 1 The MotorController is completely installed without the oper...

Page 19: ...software of the MotorController is updated the annual maintenance check The expected minimum lifetime for the MotorController is 10 years 15 1 Maintenance agreements WindowMaster offer maintenance agreements for the ventilation system Contact our service department for further information telephone 44 1536 510990 or info windowmaster co uk 15 2 Replacement 3M4 3M8 and 3KI card 1 Disconnect the 230...