System overview 

Shown below are the most common system components. In agreement with WindowMaster

®

, it is possible to use other 

components.

 

 

 

 

  

 

 

 

FutureVent™ unit

 

FutureVent

™ 

interface

 

SmartServer

 

FutureVent™ bus 

termination unit

 

 

Generel information 

Each 

FutureVent™-unit has a built in control intelligence with five analogue inputs, one analogue output and one digital output. 

The units communicate mutually via FutureVent

™ bus (FV-Bus) and must therefore be connected to 230V and FutureVent™ 

bus connection.  

In each case plan the FutureVent

™ bus cabling carefully. The cabling is planed together with WindowMaster

®

One installation can consist of many Fu

tureVent™ units installed in various rooms. In each room, a WindowMaster

®

 control unit 

is connected to the analogue and digital inputs on one of the F

utureVent™ units (Master). 

The 

FutureVent™ units have a unique ID-number (Neuron ID) and before delivery, WindowMaster

®

 programs the units. The 

unique ID-number is indicated on the unit. WindowMaster

®

 prepares and supplies documentation for each project showing 

where each unit is to be place and which unit is to be connected to the control unit.  

It is therefore of great importance that the 

FutureVent™ units are placed correct and that the control signals are 

connected the right 

FutureVent™ unit. 

Incorrect placement or wrong connected 

FutureVent™ units requires reprogramming of the installation in order for it to work.  

The most common control signals are: 
     X1-X2:  

0-10V for operation and air volume 

     X3-X10: 

on/off for one-way / balanced operation

 

 

Note all FutureVent™ units must be connected to 230V and the FutureVent™ bus.  

 

1-1 Example of floor plan 

Summary of Contents for futurevent

Page 1: ...er de CH 41 0 62 289 22 22 info windowmaster ch Other markets 45 45 37 0300 info windowmaster com FutureVent install_WFC_WFZ_UK_DK_1602 WindowMaster 2016 WindowMaster is a registered trademark used un...

Page 2: ...Checking the functionality of the installation when commissioned 5 Troubleshooting on the FutureVent installation 6 2 DK 6 System oversigt 6 Generelle informationer 6 Elektrisk installation 7 Kabelin...

Page 3: ...r control unit is connected to the analogue and digital inputs on one of the FutureVent units Master The FutureVent units have a unique ID number Neuron ID and before delivery WindowMaster programs th...

Page 4: ...an speed X For further information please see the project specific electrical documentation Service point For each four master units a service point must be established The service point is used in co...

Page 5: ...tall the SmartServer in the control panel and connect the FutureVent bus to terminal 17 and 18 Additionally supply the SmartServer with 230V on terminal 3 and 4 and establish an Ethernet connection Th...

Page 6: ..._____________ 2 DK System oversigt Herunder er de mest anvendte systemkomponenter vist Det er muligt at tilslutte andre komponenter efter aftale med WindowMaster FutureVent enheder FutureVent interfac...

Page 7: ...bindelsesdiagram Terminaler Anvendes L Fase X N Nul X PE Jord X X22 FutureVent Bus X X21 FutureVent Bus X X10 12V Out X X9 NPN Out X8 0 10V Out X7 Temp sensor X6 Fugtsensor X5 CO2 sensor X4 0V X3 Anal...

Page 8: ...et betyder at det kan kobles b de som bus og stjerne eller en kombination heraf 230V forsyning 230V forsyningskabler skal overholde g ldende regler og m maksimalt v re 1 5mm2 Det anbefales at anvende...

Page 9: ...e Aktiver digital indgangssignal p indgang X3 Observer om enheden forbliver i indbl sningsposition Fejlfinding p FutureVent anl g Enheden nulstiller ikke n r 230V forsyning tilsluttes Hvis dette ikke...

Reviews: