15
2.
For the Installer
2.5 Minimum clearances
For maintenance and servicing it is essential to comply with the minimum clearances for the walls, hydraulic
components and connection pipes.
Fig. 34 BioWIN – view from above
Fig. 35 Folding up control panel for cleaning
3
The minimum distance can be reduced by up to max. 50 mm.
4
If the room height is lower than 1900 mm, the switchboard cannot be locked anymore when lifted up (bracing has to be done on site). Also maintenance costs
can increase by a lower room height
Attention!
Follow the installation guidelines for boiler rooms!
Note!
The control panel must be folded all the way up for cleaning work – Fig. 35. Therefore,
do not
route the
exhaust pipe and connection pipes or position any hydraulic components directly
behind the control panel
.
A minimum distance of 500 mm should be observed on one side. Failure to do so will result in longer repairs.
All dimensions in mm: