Winco WL12000HE/K Installation And Operator'S Manual Download Page 9

9

2015-00

60706-233

 

d.  While the engine is warm, drain the oil and  

 

 

refill with fresh oil.

 

e.  Clean dirt and chaff from cylinder, cylinder  

 

 

head fins, blower housing, screen and 

 

 

 

muffler areas.

 

f.  Store in a clean and dry area.

OPERATING SPEED

The engine-generator must be run at the correct 

speed in order to produce the proper electrical volt-

age and frequency.

CAUTION:  EQUIPMENT DAMAGE

  The output voltage should be checked to insure 

the generator is working properly prior to connecting 

a load to the generator.  Failure to do so could result 

in damage to equipment plugged into the unit and 

possible injury to the individual.

All engines have a tendency to slow down when 

a load is applied.  When the electrical load is con-

nected to the generator, the engine is more heavily 

loaded, and as a result the speed drops slightly.  

This slight decrease in speed, together with the 

voltage drop within the generator itself, results in a 

slightly lower voltage when the generator is loaded 

to its full capacity than when running no load.  The 

slight variation in speed also affects the frequency of 

the output current.  This frequency variation has no 

appreciable effect in the operation of motors, lights 

and most appliances.  However, electronic equip-

ment and clocks will be affected if correct RPM is not 

maintained.  See Load vs. Output chart.

Although individual units and models vary slightly, 

the normal voltage and frequency of the engine-gen-

erator described in this manual are approximately as 

follows, under varying loads:

LOAD VS. OUTPUT

Generator 

Load

Speed 

(RPM)

Frequency 

(Hz)

Voltage

None

3690

61.5

125V

Half

3600

60.0

120V

Full

3510

58.5

115V

The speed of the engine was carefully adjusted at 

the factory so that the generator produces the proper 

voltage and frequency.  For normal usage, the speed 

setting should not be changed.  If the generator 

is being run continuously on a very light load, it is 

often advisable to lower the operating speed slightly.  

Reference “D” below is the speed adjustment  for 

this engine.  

CAUTION:  EQUIPMENT DAMAGE

 

 

SPEED ADJUSTMENTS SHOULD ONLY BE 

MADE BY A QUALIFIED SERVICE TECH.  

Whenever making any speed adjustments, check 

the unit with a voltmeter and a frequency meter 

or tachometer and be sure the voltage and speed 

are correct. 

Lower voltage may damage both the generator and 

any load connected to it.  Running the engine at ex-

cessively high speeds results in high voltage, which 

may significantly shorten the life of appliances being 

used.

Output voltage should be checked periodically to 

ensure continued proper operation of the generat-

ing plant and appliances.  If the generator is not 

equipped with a voltmeter, it can be checked with a 

portable meter.  

CONNECTING THE LOADS

APPLYING THE LOADS

Allow the engine to warm up for two or three minutes 

before applying any load. This will allow the engine 

to reach normal operating temperature and oil to cir-

culate throughout the engine. A short warm-up time 

will permit the engine to work more efficiently when 

the load is applied and will reduce the wear in the 

engine, extending its life.  

Receptacles have been provided to allow loads to 

be connected to the generator. The loads should 

be added one at a time.  If a large motor is being 

started; or multiple motors are being started, they 

should be started individually and the largest should 

be started first.

D

Summary of Contents for WL12000HE/K

Page 1: ...INSTALLATION AND OPERATORS MANUAL INDUSTRIAL PORTABLE WL12000HE K WINCO INC 225 S CORDOVA AVE LE CENTER MN 56057 507 357 6821 SERVICE DEPT 507 357 6831...

Page 2: ...5 Battery Installation 6 Basic Operation 7 INITIAL START UP 8 Manual Starting 8 Electric Starting 8 Stopping Storage 9 Operating Speed 9 CONNECTING THE LOADS 10 Wiring 10 ENGINE CARE 11 GENERATOR CAR...

Page 3: ...ren c Do not smoke or use open flame near the generator set or fuel tank d Keep a fire extinguisher nearby and know its proper use Fire extinguishers rated ABC by NFPA are appropriate e Store fuel onl...

Page 4: ...ere are 3rd party companies making enclosures for generators that have been properly engineered The use of these 3rd party enclosures is acceptable as long as they have been certified and meet current...

Page 5: ...be on a level surface before you check or add oil to the system The necessity of using the correct oil and keeping the crankcase full cannot be overemphasized En gine failures resulting from inadequat...

Page 6: ...time it is best to drain old fuel from the engine and replace with fresh fuel before attempting to start See the engine manual for special instruction for operating this unit at over 5000 feet BATTER...

Page 7: ...list in the back of this manual for future refer ence OIL ALERT SYSTEM This WINCO Industrial generator is equipped with a low oil shutdown system This Honda engine uses an float switch mounted inside...

Page 8: ...urn the engine switch to the OFF position If the fuel tank is equipped with a valve turn the fuel valve to the CLOSED or OFF position 6 7 3 1 2 ENGLISH STOPPING THE ENGINE M MI IN N M MI IN N START EN...

Page 9: ...oltage None 3690 61 5 125V Half 3600 60 0 120V Full 3510 58 5 115V The speed of the engine was carefully adjusted at the factory so that the generator produces the proper voltage and frequency For nor...

Page 10: ...nerator receptacles Before plugging in all the tools and cord sets recheck the rating of the genera tor set Be sure it can handle the intended load and is compatible with the voltage phase and current...

Page 11: ...ore starting the engine If the engine has been running allow it to cool Refuel carefully to avoid spilling fuel It may be necessary to lower the fuel level depending on operating conditions After refu...

Page 12: ...e cover 4 Spark Plug Replace annually or every 300 hours of operation Always replace with the same spark plug that came in the engine and check gap before installing Spark plug gap is 0 030 Poor spark...

Page 13: ...equipped with spark arrest ers the spark arrester must be removed every 50 hours for cleaning and inspection Replace if dam aged TROUBLESHOOTING PROBLEM SYMPTOMS POSSIBLE CAUSES Won t Start Low Oil Le...

Page 14: ...2015 00 14 60706 233 CONTROL PANEL WIRING DIAGRAM...

Page 15: ...earest WINCO Authorized Service Center or to WINCO Inc at Le Center Minnesota THERE IS NO OTHER EXPRESS WARRANTY To the extent permitted by law any and all warranties including those of merchantabilit...

Page 16: ...RER S WARRANTY COVERAGE The evaporative emission control system is warranted for two years If any evaporative emission related parts on your equipment are defective the parts will be repaired or repla...

Reviews: