12

OPM-139/E

2. If the generator set is connected to an existing 

  distribution system, a fully isolated manual transfer switch 

  must be installed. The transfer switch prevents damage to 

  the generator and the other circuit components if main 

  line power is restored while the generator is connected. 

  Installing a transfer switch also permits the use of normal 

 fusing.

3.Many homes and construction sites are wired for at least 

  60 to 100 Amp entrance service, much greater than the 

  capacity of this portable generator. When installing 

  the generator at these sites, a secondary emergency 

  distribution panel may have to be installed. The 

  emergency distribution panel must be installed by a 

  licensed electrician according to all applicable codes. 

  The electrician will move the critical circuits to be 

  powered during the outage to the emergency panel. 

  Keep in mind only a limited amount of amperage is 

  available from the generator set. Some circuit breakers 

  may still have to be turned off to prevent an overload on 

  the generator during the initial start up. See the 

  nameplate on your generator for the amperage 

  capabilities of your unit.

CAUTION: EQUIPMENT DAMAGE

Failure to properly limit and balance the load applied to 
the generator will cause the generator to produce low 
voltage and may damage the engine generator set. It may 
also cause severe damage to the loads connected to the 
generator at that time. Improper loading of the generator 
set constitutes abuse and will not be covered by warranty.

Summary of Contents for WL12000HE-03/A

Page 1: ...ld ever need to contact us concerning this unit it will help us to respond to your needs faster MODEL __________________________________________________ SERIAL NUMBER _________________________________...

Page 2: ...E 17 WIRING DIAGRAM 18 WIRING DIAGRAM 19 CA EVAP EMISSION CONTROL 20 LIMITED WARRANTY 20 SAVE THESE INSTRUCTIONS This manual contains important instructions that should be followed during installation...

Page 3: ...set or fuel tank D Keep a fire extinguisher nearby and know its proper use Fire extinguishers rated ABC by NFPA are appropriate E Store fuel only in an approved container and only in a well ventilated...

Page 4: ...Generator Model Number S20FS 160 A Part Number 351836 1 Rotor Resistance 6 57 Ohms Stator Resistance 0 124 Ohms Cap Winding Resistance 0 60 Ohms Capacitors 31 5 mF Capacitor Part Number 300323 112 ENG...

Page 5: ...e performance these units should never be run in small compartments without positive fresh air flow RESTRICTED USES DO NOT remove from the cradle assembly Removal of the generator from the cradle asse...

Page 6: ...out the same amount of current to run them whether they are Repulsion Induction RI Capacitor Cap or Split Phase SP type If the electric motor is connected to a hard starting load such as an air compre...

Page 7: ...ine in a level position fill with the recommended oil to the upper limit mark on the oil level dipstick Running the engine with a low oil level can cause engine damage This type of damage is not cover...

Page 8: ...EGATIVE battery terminal to GROUND For your safety always connect the positive battery cable to the bat terminal first Then connect the negative battery cable to the Bat terminal Make sure all connect...

Page 9: ...e the starter Turn the engine switch to the START position and hold it there until the engine starts If the engine fails to start within 5 seconds release the engine switch and wait at least 10 second...

Page 10: ...s and models vary slightly the normal voltage and frequency of the engine generator described in this manual are approximately as follows under varying loads LOAD vs OUTPUT Generator Load Speed RPM Fr...

Page 11: ...sist you The NFPA 70 250 34 35 are good technical references STANDARD PORTABLE GENERATOR Your WINCO portable generator ships with a bonded neutral You can safely use this generator without external gr...

Page 12: ...ution panel must be installed by a licensed electrician according to all applicable codes The electrician will move the critical circuits to be powered during the outage to the emergency panel Keep in...

Page 13: ...ual are approximately as follows under varying loads LOAD vs OUTPUT Generator Load Speed RPM Frequency Hz Voltage 120V Recpt 240V Recpt None 3690 61 5 120V 240V Half 3600 60 0 120V 240V Full 3510 58 5...

Page 14: ...from the receptacles attached to either A or B output legs This generator is capable of producing 45 Amps of 240 volt current at C Check the appliance or tool nameplates for the current and voltage t...

Page 15: ...o length A Start the engine and warm it up stop the engine and remove the spark plug wire to prevent it from accidentally being started B This engine has an oil drain valve for your convenience Attach...

Page 16: ...nt in clean engine oil and squeeze out all the excess before reinstalling it The engine will smoke when started if too much oil is left in the foam H Clean the dirt from the inside of the air cleaner...

Page 17: ...igh pressure spray could contaminate the fuel system and the generator components 1 Keep the air inlet screen on both the engine and generator free of any dirt or debris to ensure proper cooling At le...

Page 18: ...18 OPM 139 E WIRING DIAGRAM WL12000HE 03 A WL12000HE 03 C...

Page 19: ...19 OPM 139 E WIRING DIAGRAM G1 G3 G3 G3 G3 G3 G3 G3 N G1 GND GND GND GND GND N N N N N G1 G1 G1 G1 G1 G1 G1 WL12000HE 03 B WL12000HE 03 D...

Page 20: ...nd Purchaser s sole remedy for a failure under this warranty shall be limited to the repair of the product At WINCO s option material found to be defective in material or workmanship under normal use...

Reviews: