Winco W100PTOS Owner'S Manual Download Page 8

Page 6

60706-160

3117-20

6. Make sure that the electrical loads to be powered by the
generator will not exceed the current ratings of the generator,
receptacle, or cord set which will supply the current.

7. Check all electrical connections in the system to be
energized by the generator. Make sure the connections are
correct and tight and the load disconnect plug (if provided) is
fully seated in the receptacle.

8. Make sure all loads are turned off. Do not start the generator
under load.

GENERATOR STARTING PROCEDURE

1.  With the power take-off drive disengaged, start the engine
which will drive the generator. Run the engine long enough to
warm it up before proceeding, so that it will run smoothly and
achieve full power under generator load.

2. With engine idling, engage the power take-off drive.

3. Watch the frequency meter on the generator and slowly
increase engine speed until the frequency reaches approxi-
mately 60 Hz.  The voltage output of the generator is controlled
by an Automatic Voltage Regulator (AVR).  Before turning on
any load check your voltage output from the generator using a
volt/ohm meter.  If the voltage is either high or low adjust the
voltage level by turning the voltage adjustment screw on the
AVR.  The AVR is located inside the generator control cabinet.
Once the proper voltage level is set the AVR should bring the
voltage back to the same level each time the unit is started up.
But as a precaution it should be checked each time you use
the generator. As quick check you can plug in a troublelight
and check for normal brightness.

4. With engine and generator running smoothly, switch on the
electrical load while watching the frequency meter.

NOTE: Equipment Damage
If the load includes motors turn them on one at a time, highest
starting current motor first, next highest second, etc.

Adjust engine throttle to keep generator output under load at
60 Hz. If the engine is equipped a with governor, it may
automatically adjust the throttle as the load changes and keep
the generator output at the proper level. However, some
governors are not sensitive enough to maintain proper output
under changing loads, and in such cases the frequency will
have to be monitored closely and manually adjusted .

GENERATOR SHUTDOWN PROCEDURE

1. Switch off electrical load.

2. Reduce speed of engine driving generator to idle.

3. Disengage power take-off drive, and allow generator to
coast to a stop.

WARNING: Personal Injury
Never try to manually stop the generator.  Always let it coast
until it stops.

3. Make sure the drive shaft (tumbling bar) is assembled with
its universal joint knuckles “synchronized,” as illustrated in
Figure 7. If knuckles are not synchronized, the bar will chatter
when rotating, which will cause the generator output voltage to
flicker.

DANGER: Personal Injury

POWER TAKE-OFF MUST BE DISENGAGED AT THIS TIME.

4. Couple the tractor to the generator with the drive shaft
(tumbling bar). Couple the tumbling bar to the generator input
shaft first, then to the power take-off shaft. Check alignment of
tractor, power take-off shaft (tumbling bar), and generator input
shaft should form a straight (or nearly straight) line, with less
than 15° misalignment between the shafts. Misalignment will,
stress the drive line and  cause generator output voltage to
flicker.

CAUTION:

Make sure that all tumbling bar lock pins are engaged and
that all safety shields are in place before operating the PTO
generator.

5. Make sure no binding exists in generator or gear box. If
binding is found, locate the cause and correct it before
proceeding.

Figure 7

Figure 6

Summary of Contents for W100PTOS

Page 1: ...60706 160 W100PTOS W105PTOT W135PTOS W145PTOT W150PTOS Tractor Drive PTO Generators OWNERS MANUAL INSTALLATION AND OPERATION INSTRUCTIONS SAFETY FIRST READ THIS MANUAL BEFORE OPERATING YOUR GENERATOR ...

Page 2: ...TION 5 Pre Start Checks 5 Starting Procedure 6 Stopping 6 MAINTENANCE 7 Lubrication 7 Cleaning 8 Storage 8 TroubleShootingTable 8 GENERATORCONNECTIONS 120 240 Volt Single Phase 10 120 240 Volt Three Phase 10 120 208 Volt Three Phase 11 277 480 Volt Three Phase 11 GENERATORRECEPTACLEPANELS 12 Convenience Receptacle Wiring 13 36MONTHWARRANTY 14 PROPER USE AND INSTALLATION You must be sure your new g...

Page 3: ...n and or fire a Keep a fire extinguisher nearby and know its proper use Fire extinguishers rated ABC by NFPA are appropriate 3 DEADLY EXHAUST GAS Exhaust fumes from any engine contain carbon monoxide an invisible odorless and deadly gas that must be mixed with fresh air a Operate only in well ventilated areas b Never operate indoors 4 NOISE HAZARD Excessive noise is not only tiring but continual e...

Page 4: ...ay the subpack carton with the large carton 4 Open the subpack carton and make sure it contains a Generator instruction manual b Load disconnect plug disassembled in bag 5 Remove the four bolts which hold down the generator feet to the pallet 6 Lift the generator from the pallet by means of the lifting eye on the top of the generator 7 Inspect the generator carefully for freight loss or damage If ...

Page 5: ...less than 15 degrees during generator operation even though the mechanical design of the tumbling bar would allow greater misalignment The following wire sizes are recommended for each unit Generator Size Model AWG Insulation W100PTOS 4 0 Neoprene THHN W105PTOT 4 0 Neoprene THHN W135PTOS 350MCM THHN NO Plug Provided W145PTOT 4 0 THHN NO Plug Provided W150PTOS 500MCM THHN NO Plug Provided WARNING E...

Page 6: ...ns should install electrical wiring Wiring must conform to all applicable national state and local codes Reference National Fire Protection Association Manual No 70 National Electrical Code DANGER PERSONALINJURY IF THE GENERATOR IS TO BE USED AS A STANDBY POWER SOURCE A SPECIAL DISCONNECT SWITCH MUST BE INSTALLED TO SEPARATE THE GENERATOR AND THE COMMERCIAL POWER LINES THE DISCONNECT MUST ISOLATE ...

Page 7: ... its starting current which is a lot higher Motor starting current requirements vary greatly by motor size and type Repulsion induction type motors are the easiest to start typically using 1 1 2 to 2 1 2 times as much current to start as to run capacitor type motors usually require 2 to 4 times as much current to start as to run split phase type motors are the hardest to start normally using 5 to ...

Page 8: ...TE EquipmentDamage If the load includes motors turn them on one at a time highest starting current motor first next highest second etc Adjust engine throttle to keep generator output under load at 60 Hz If the engine is equipped a with governor it may automatically adjust the throttle as the load changes and keep the generator output at the proper level However some governors are not sensitive eno...

Page 9: ...he generator The drive shaft tumbling bar requires greasing Keep the universal joints in the coupling shaft free from grease and dirt buildup NOTE Do not over lubricate the universal joints See Figure 8 for recommended lubrication schedule for the coupling shaft Check the generator gear case oil level before each use of the generator Maintain the oil level at oil level plug height Figure 6 illustr...

Page 10: ...rloaded 2 Reduce load if it is higher than the rated capacity of the generator See generator nameplate 3 Inadequate engine horsepower 3 Generator requires 2 HP 1000 watts output Obtain larger engine if necessary 4 Defective or mis adjusted AVR 4 Repair adjust or replace as required 5 Replace the oil level check plug 6 Replace the breather CLEANING INSPECTINGTHEGENERATOR Use a vacuum cleaner or dry...

Page 11: ...er take off misalignment 1 Correct misalignment It should be less than 15 degrees vibration excessive 2 Loose mounting nuts and bolts 2 Tighten mounting nuts and bolts repair hold down stud or hold down studs mountings 3 Universal joints in coupling 3 Repair or replace defective parts shaft worn or dry 4 Defective bearings 4 Check for possible causes Replace defective bearings Generator 1 Poor ven...

Page 12: ...Page 10 60706 160 3117 20 GENERATOR CONNECTIONS 120 240 VOLT SINGLEPHASE GENERATOR CONNECTIONS 120 240 VOLT THREEPHASE ...

Page 13: ...Page 11 60706 160 3117 20 GENERATOR CONNECTIONS 120 208 VOLT THREEPHASE GENERATOR CONNECTIONS 277 480 VOLT THREEPHASE ...

Page 14: ...Page 12 60706 160 3117 20 GENERATOR RECEPTACLE PANEL W105PTOT 4 W105PTOT 17 GENERATOR RECEPTACLE PANEL W100PTOS 3 GENERATOR RECEPTACLE PANEL W105PTOT 18 ...

Page 15: ...60 3117 20 GENERATOR RECEPTACLE PANEL ON MODELS W135PTOS 3 W145PTOT 4 W145PTOT 17 W150PTOS 3 GENERATOR RECEPTACLE PANEL ON MODEL W145PTOT 18 GENERATOR CONVENIENCE RECEPTACLE WIRING ON ALL MODELS EXCEPT 480 VOLT UNITS ...

Page 16: ...mitationsonthedurationofanimpliedwarranty andsomestatesdonotallow the exclusion or limitation of incidental or consequential damages so that above limitation or exclusion may notapplytoyou Thiswarranty givesyouspecificlegalrights youmayhaveother rights which vary from state to state This warranty is limited to bench labor and parts only no allowance will be made for travel time or removalandreinst...

Reviews: