Winco W10000VE/A Installation And Operator'S Manual Download Page 8

8

REV A

OPM-113

OPERATING SPEED

The engine-generator must be run at the correct speed in order to 

produce the proper electrical voltage and frequency.

CAUTION: EQUIPMENT DAMAGE

The output voltage should be checked to ensure the generator is 

working properly prior to connecting a load to the generator. Failure to 

do so could result in damage to equipment plugged into the unit and 

possible injury to the individual.

All small engines that use a governor spring have a tendency to slow 

down when a load is applied. When the electrical load is connected 

to the generator, the engine is more heavily loaded, and as a result, 

the speed drops slightly. This unit is equipped with an AVR that 

automatically adjusts output depending on RPM speed and applied 

load. The slight variation in speed also affects the frequency of the 

output current. This frequency variation has no appreciable effect 

in the operation of motors, lights, and most appliances. However, 

electronic equipment and clocks may be affected if correct RPM is not 

maintained. See Load vs. Output chart.

Although individual units and models vary slightly, the normal voltage 

and frequency of the engine-generator described in this manual are 

approximately as follows, under varying loads:

LOAD vs. OUTPUT

Generator 

Load

Speed 

(RPM)

Frequency 

(Hz)

Voltage

None

3690

61.5

120V

Half

3600

60.0

120V

Full

3510

58.5

120V

The speed of the engine was carefully adjusted at the factory so that 

the generator produces the proper voltage and frequency. For normal 

usage, the speed setting should not be charged. If the generator is 

being run continuously on a very light load, it is often advisable to lower 

the operating speed slightly. 

Reference “A” in the following image is the speed adjustment for this 

engine.

CAUTION: EQUIPMENT DAMAGE

SPEED ADJUSTMENTS SHOULD ONLY BE MADE BY A QUALIFIED 

SERVICE TECH. 

Whenever making any speed adjustments, check the 

unit with a voltmeter and a frequency meter or a tachometer and be 

sure the voltage and speed are correct.

Output voltage should be checked periodically to ensure continued 

proper operation of the generating plant and appliances. If the 

generator is not equipped with a voltmeter, it can be checked with a 

portable meter.

A

CONNECTING THE LOADS

APPLYING THE LOADS

Allow the engine to warm up for two or three minutes before applying 

any load. This will allow the engine to reach normal operating 

temperature and oil to circulate throughout the engine. A shot warm-up 

time will permit the engine to work more efficiently when the load is 

applied and will reduce the wear in the engine, extending its life.

Receptacles have been provided to allow loads to be connected to the 

generator. The loads should be added one at a time. If a large motor 

is being started: or multiple motors are being started, they should be 

started individually and the largest should be started first.

CAUTION: EQUIPMENT OVERLOAD

Keep the generator load within in the generator and receptacle 

nameplate rating. Overloading may cause damage to the generator 

and/or the loads.

Most electric tools and appliances will have the voltage and amperage 

requirements on their individual nameplates. When in doubt, consult 

the manufacturer or a local electrician. The nameplate amperage rating 

for electric motors can be misleading. See “Starting Electric Motors” in 

the Unit Capabilities. 

The engine governor will automatically adjust itself to the load. 

No harm to the generator will result if it is operated with no load 

connected. Proper utilization of the receptacles located on the control 

panel is necessary to prevent damage to either the receptacles or 

the generator. The generator is a limited source of electrical power, 

therefore, pay special attention to the receptacle and generator ratings. 

The nameplate rating can be obtained through a single receptacle as 

long as the receptacles amperage rating is not exceeded.

GROUNDING

All units must be grounded. Drive a 3/4 or 1” copper pipe or rod into 

the ground close to the engine-generator set. The pipe must penetrate 

moist earth. Connect an approved ground clamp to the pipe. Run a 

no. 10 Awg wire from the clamp to the generator ground lug on the 

receptacle panel. Do not connect to a water pipe or to a ground used 

by a radio system. The engine-generators covered in this manual were 

designed primarily for portable use. If you are connecting into a building 

wiring system that is already grounded using the 14-60 4 wire plug, you 

do not have to ground the unit.

WARNING: PERSONAL DANGER

DO NOT OPERATE THIS GENERATOR INDOORS,

 

The unit should 

be stored in a warm, dry location. During a power outage, move the 

unit outdoors to a flat, dry location such as a driveway or sidewalk. 

Summary of Contents for W10000VE/A

Page 1: ...WINCO INC 225 S CORDOVA AVE LE CENTER MN 56057 507 357 6821 SERVICE DEPT 507 357 6831 www wincogen com INSTALLATION AND OPERATORS W10000VE A GENERATOR MANUAL...

Page 2: ...quality precision engineered generator designed and tested to give you years of satisfactory service To get the best performance from your new generator it is important that you carefully read and fo...

Page 3: ...nsible person A Do not allow anyone to operate the generator without proper instruction B Guard against electric shock C Avoid contact with live terminals or receptacles D Use extreme care if operatin...

Page 4: ...ent amps to start them than to run them Some motors particularly low cost split phase motors are very hard to start and require 5 to 7 times as much starting current as running current Capacitor motor...

Page 5: ...l level may cause excessive wear which can be cumulative GASOLINE When using gasoline always use fresh clean unleaded fuel The engine is certified to operate on unleaded gasoline with a minimum octane...

Page 6: ...For your safety always connect the positive battery cable to the bat terminal first Then connect the negative battery cable to the bat terminal Make sure all connections are clean an tight Reverse the...

Page 7: ...Rotate the key switch C briefly to the START position Repeat if necessary NOTE The starter life is improved by using shorter cycles with time to cool off between cranking cycles Do NOT operate the sta...

Page 8: ...ING THE LOADS Allow the engine to warm up for two or three minutes before applying any load This will allow the engine to reach normal operating temperature and oil to circulate throughout the engine...

Page 9: ...N EQUIPMENT DAMAGE Failure to properly limit and balance the load applied to the generator will cause the generator to produce low voltage and may damage the engine generator set It may also cause sev...

Page 10: ...t with fresh clean oil e Install the oil lter by hand until the gasket contacts the oil lter adapter then tighten the oil lter 1 2 to 3 4 turns f Replace oil drain plug g Remove oil ller plug and re l...

Page 11: ...rwise damaged replace it Using damaged or cracked receptacles can be both dangerous to the operator and destructive to the equipment CLEANING Remove dirt and debris with a cloth or brush DO NOT use hi...

Page 12: ...e consumables or labor This warranty does not cover travel time mileage or labor for removal or re installation of WINCO product from its application Normal wear and tear Costs of rental equipment WIN...

Reviews: