DSE 3110 CONTROL
FAULT CODES
PREVENTIVE
MAINTENANCE
Reasonable care in preventive maintenance will
insure high reliability and a long life for the engine
generator set and Automatic Transfer Switch.
*****************
***** WARNING *****
*****************
When performing any type of maintenance on this
equipment make sure the selector switch on the
generator is in the off position. If you are working in
the Automatic Transfer Switch, confirm with a reli-
able meter that all power has been disconnected.
AUTOMATIC TRANSFER SWITCH
Clean and inspect the switch once a year. de-ener-
gize all power sources, both line and generator set,
then brush and vacuum away any excessive dust
or dirty accumulation. You can at this time with the
contactor de-energized remove the contactor covers
and check the contacts. Make sure contacts are
clean and not burned or pitted.
ENGINE GENERATOR SET
Service the engine in accordance with the engine
manufacturers manual provided with your new
equipment. Routinely remove debris and dirt from
around the inside generator enclosure. Insure that
the air intakes are free from leaves and other debris
at all times.
Clean and inspect battery terminals a least twice a
year. Check the battery water level at least twice a
year also.
Other than keeping the generator set clean and
free of debris there is no other routine or preventa-
tive maintenance required, as long as the generator
is run biweekly to keep it dry and in good working
order.
COLD WEATHER OPERATION
Extreme cold weather operation requires special
considerations. Higher CCA batteries are required
for cold weather starting, 650 CCA or larger are rec-
ommended. In addition you should consider install-
ing an oil heater kit and a battery warmer for reliable
starting during cold weather.
MAINTENANCE LOG
DATE WORK PERFORMED
225 S. CORDOVA AVE.
LECENTER, MN 56057
507-357-6821
SERVICE DEPT.
507-357-6831
DESCRIPTION
AUXILIARY INPUTS
Auxiliary inputs can be user configured and will display
the message as written by the user.
FAIL TO START
The engine has not fired after the preset number of start
attempts
FAIL TO STOP
The module has detected a condition that indicates that
the engine is running when it has been instructed to stop.
NOTE:- ‘Fail to Stop’ could indicate a faulty oil pressure sensor
- If engine is at rest check oil sensor wiring and configuration.
LOW OIL LEVEL
The module detects that the engine oil level has fallen
below the low oil level pre-alarm setting level after the
Safety On
timer has expired.
ENGINE HIGH OIL
TEMPERATURE
The module detects that the engine oil temperature has
exceeded the high engine temperature pre-alarm setting
level after the
Safety On
timer has expired.
UNDERSPEED
The engine speed has fallen below the underspeed pre
alarm setting
OVERSPEED
The engine speed has risen above the overspeed pre
alarm setting
BATTERY UNDER
VOLTAGE / BATTERY
OVER VOLTAGE
The DC supply has fallen below or risen above the low/
high volts setting level.
GENERATOR UNDER
VOLTAGE
The generator output voltage has fallen below the pre-set
pre-alarm setting after the
Safety On
timer has expired.
GENERATOR OVER
VOLTAGE
The generator output voltage has risen above the pre-set
pre-alarm setting.
GENERATOR UNDER
FREQUENCY
The generator output frequency has fallen below the
pre-set pre-alarm setting after the
Safety On
timer has
expired.
GENERATOR OVER
FREQUENCY
The generator output frequency has risen above the pre-
set pre-alarm setting.
C