Shower control
WimTec PROOF S6
21
EN
PROOF S6
Configuring the programs & functions
Einstellregler:
D.
Range control
to detect user interaction
Sensor range preset to 50 cm
(configurable from 15 cm to
50 cm).
Sets the infrared sensor range
from 15 cm – 50 cm.
Automatic range adjustment
within the preset maximum
range.
E.
Time control
set to safety flow arrest after
10 min (configurable from
10 s to 10 min).
self-closing program mode:
10 s to 60 s.
After the configured maximum
flow time has elapsed, the
water stops automatically to
prevent unintentional conti-
nuous activation.
F.
Interval control
for stagnation rinse
(configurable from 3 h to 48 h).
If the fitting has not been
used for the set period, the
device will automatically
perform a 10 s rinse to flush
stagnant water from the
pipes.
Program activation – DIP switches 1 and 2:
Program
DIP switch 1
DIP switch 2
Description
Semi automatic mode
1)
OFF
ON
Page 29
Fully automatic mode
ON
ON
Page 30
Manual mode
OFF
OFF
Page 31
DIP switches:
1)
Preset program.
Function activation – DIP switches 3–6:
DIP switch
Function
Factory setting
Description
3
Shut-off delay ON = 5 s / OFF = 2 s
OFF
4
Warm water rinse
ON
Page 32
5
Not allocated
-
-
6
Stagnation rinse
OFF
Page 34