Wilo Yonos MAXO Series Installation And Operating Instructions Manual Download Page 7

EN

Installation

19

5.3 

Preparing the installation

 

Branch off the safety feed ahead of the pump when 

installing in feed of open systems (EN 12828).

 

Complete all welding and brazing tasks.

 

Flush unit.

 

Arrange shut-off devices in front of and behind the 

pump. Laterally align the shut-off device above the pump 

so that the leakage water does not drip on the control 

module.

 

Make sure that the pump can be installed free of me-

chanical stresses.

 

Allow a 10 cm distance around the control module so that 

it does not overheat.

 

Observe permissible installation position 

➜ 

Fig. 

5

.

When installing outdoor observe detailed 

instructions on the Internet 

 page 2.

5.4 

Align

The motor head must be aligned according to installation 

position.

 

Check permissible installation positions 

➜ 

Fig. 

5

.

 

Dismantle motor head and carefully turn 

➜ 

Fig. 

6

.  

Do not remove motor from pump housing.

ATTENTION

 

Damage to the gasket causes leakage.

 

Do not remove gasket.

5.5 

Installation

➜ 

Fig. 

7

 to 

10

 

Flange-end pump PN 6

DN 32

DN 40

DN 50

Screw diameter

M12

Strength class

≥ 4.6

Tightening torque

40 Nm

Screw length

≥ 55 mm

≥ 60 mm

DN 65

DN 80

DN 100

Screw diameter

M12

M16

Strength class

≥ 4.6

Tightening torque

40 Nm

95 Nm

Screw length

≥ 60 mm

≥ 70 mm

Flange-end pump PN 10 and PN 16  

(no combination flange)

DN 32

DN 40

DN 50

Screw diameter

M16

Strength class

≥ 4.6

Tightening torque

95 Nm

Screw length

≥ 60 mm

≥ 65 mm

Summary of Contents for Yonos MAXO Series

Page 1: ...erings og driftsveiledning 85 FI Asennus ja k ytt ohje 92 DA Installations og driftsvejledning 99 Wilo Yonos MAXO D 2 172 446 Ed 01 2016 08 Wilo de Einbau und Betriebsanleitung en Installation and ope...

Page 2: ...17 18 19 6 6 7 8 9a 5 5 9b 10 5 5 11 12 13 14 15 16 5 6 6 6 6 3 6 6 7 2 20...

Page 3: ...ble place at all times Observe instructions and labelling on the pump Observe local regulations where the pump is installed Observe details instructions on the Internet page 2 1 2 Original instruction...

Page 4: ...nce on the delivery rate 2 1 Type key Example Yonos MAXO D 32 0 5 11 Yonos MAXO Pump designation D Double pump 32 Flange connection DN 32 0 5 11 0 5 Minimum delivery head in m 11 Maximum delivery head...

Page 5: ...uthorised conversions Use exclusively authorised accessories and authorised spare parts Never operate with phase angle control 3 2 Operator responsibilities Keep children and people with reduced physi...

Page 6: ...only for heating applications 4 3 Transport inspection Following delivery immediately check for damage and in tegrity Where necessary make a complaint immediately 4 4 Transportation and storage Only c...

Page 7: ...lling outdoor observe detailed instructions on the Internet page 2 5 4 Align The motor head must be aligned according to installation position Check permissible installation positions Fig 5 Dismantle...

Page 8: ...power supply or IT networks During external connection of the pump deactivate a pulse of the voltage for example phase angle control Switching the pump via triacs solid state relays must be examined...

Page 9: ...ntrol module has failed DANGER Danger to life through voltage transmission if mains and SSM pipe are led together through a 5 wire cable Do not connect SSM pipe to protective low voltage Use 5 x 1 5 m...

Page 10: ...caighde in chomhchuibhithe na hEorpa d dtagra tear sa leathanach roimhe seo HR Hrvatski HU Magyar EZ IZJAVA O SUKLADNOSTI EK MEGFELEL S GI NYILATKOZAT i uskla enim europskim normama navedenim na preth...

Page 11: ...rupa y netmeliklerine ve ulusal kanunlara uygun oldu unu beyan etmektedir 2006 42 2014 30 2009 125 Machines 2006 42 EG Elektromagnetische Compatibiliteit 2014 30 EG Energiegerelateerde producten 2009...

Page 12: ...tirilmesini isteme haklar ndan birini kullanabilir 4 T keticinin bu haklardan cretsiz onar m hakk n se mesi durumunda sat c i ilik masraf de i tirilen par a bedeli ya da ba ka herhangi bir ad alt nda...

Page 13: ......

Page 14: ...wilo it Kazakhstan WILO Central Asia 050002 Almaty T 7 727 312 40 10 info wilo kz Korea WILO Pumps Ltd 20 Gangseo Busan T 82 51 950 8000 wilo wilo co kr Latvia WILO Baltic SIA 1019 Riga T 371 6714 522...

Page 15: ...WILO SE Nortkirchenstra e 100 D 44263 Dortmund Germany T 49 0 231 4102 0 F 49 0 231 4102 7363 wilo wilo com www wilo com...

Reviews: