Faults, causes and remedies
192
WILO SE 2022-05
Settings
Yonos GIGA2.0
Yonos GIGA2.0 ... R1
Pump kick time interval
24 h
24 h
Basic function
Control mode
Control mode
Ramp time
0 s
0 s
Automatic PWM frequency
reduction
switched off
switched off
Table 32:
Factory settings
17
Faults, causes and remedies
WARNING
Have faults remedied by qualified personnel only! Observe safety in-
structions.
In the event of malfunctions occurring, the fault management system provides pump
performance and functionalities that can still be achieved.
A fault that has occurred is checked continuously if technically possible and, if possible,
emergency operation or control mode is restored.
Malfunction-free pump operation is resumed as soon as the cause of the malfunction
no longer exists. Example: The electronic module is again cooled down.
NOTICE
If the pump behaves incorrectly, check that the analogue and digital inputs are con-
figured correctly.
If the malfunction cannot be rectified, consult a specialist technician or the nearest
Wilo customer service or representative location.
17.1
Mechanical faults without error
messages
Faults
Causes
Remedies
Pump does not start or
stops working.
Cable terminal loose.
Check all cable connections.
Pump does not start or
stops working.
Fuse protection defect.
Check fuses; replace faulty
fuses.
Pump runs at reduced
performance.
Stop valve on the discharge
side throttled.
Slowly open the stop valve.
Pump runs at reduced
performance.
Air in the suction line
Eliminate leakage at flanges.
Vent pump. In case of visible
leakage, replace the mechan-
ical seal.
Pump makes noises.
Cavitation due to insuffi-
cient suction pressure.
Increase the suction pressure.
Observe the minimum inlet
pressure at the suction port.
Check slide valve and filter on
the suction side and clean if
need be.
Pump makes noises.
Motor has bearing damage.
Have the pump checked by
Wilo customer service or a spe-
cialised service centre and re-
paired if necessary.
Table 33:
Mechanical faults
17.2
Error messages
Displays an error message on the display
ƒ
The status display will be in red colour.
ƒ
Error message, error code (E...).
The pump does not pump if an error has occurred. If the pump identifies as part of
permanent monitoring that the cause of the error no longer applies, the error mes-
sage is revoked and operation resumes.
Summary of Contents for Yonos GIGA2.0-D
Page 2: ......
Page 3: ...Fig I Yonos GIGA2 0 I D DN 32 DN 80 D E D...
Page 4: ...Fig II Yonos GIGA2 0 I D DN 100 DN 125 D D E...
Page 5: ...5 Deutsch 6 English 108 Fran ais 208 Nederlands 314...
Page 416: ......
Page 417: ......
Page 418: ......
Page 419: ......
Page 420: ......
Page 421: ......
Page 422: ......
Page 423: ......