Installation and electrical connection

16

WILO SE 2020-09

Bus topology

The bus topology consists of multiple participants (e.g. pumps, control devices and a
gateway) that have been connected in series. The participants are connected via a
shared cable.
The bus must be terminated at both ends of the cable. This is done for the two ex-
ternal participants. All other participants must not have activated termination.
Since the Wilo-Smart Gateway does not provide termination, the Gateway must not
be installed at the end of a bus line (Fig. 2).
If only one pump with Wilo Net is installed on the Gateway, the termination only has
to be activated on the one pump as an exception.

All bus subscribers must be assigned an individual address (Wilo Net ID). Please be
aware that twin-head pumps in the Wilo Net consist of two participants, both of
which must be adjusted accordingly in the Wilo Net settings. This Wilo Net ID is set in
the respective participant.

For more detailed information on how to set the Wilo Net ID and termination on the
respective connected device, refer to the respective installation and operating in-
structions.

The Gateway is preset to Wilo Net ID “21”.

In order to establish the Wilo Net connection, the three 

H, L, GND

 terminals are wired

with a communication cable from pump to pump to Gateway to pump. Use shielded
cables for cable lengths ≥ 2 m.

Up to 20 participants can be connected to Wilo Net 1. Twin-head pumps consisting
of two participants. For twin-head pumps, please also be aware that a maximum of
5 twin-head pumps can be operated in one Wilo Net segment. As well as the maxi-
mum of 5 twin-head pumps in a Wilo Net segment, up to 10 further single pumps can
still be integrated.
We anticipate that another 20 participants can be connected to Wilo Net 2 with the
future software functions that are planned for the Gateway. The available Wilo Net
IDs are reassigned in the second segment, so they can match the IDs used in Wilo
Net 1. If the participants are correctly connected to the Wilo-Smart Gateway and Wilo
Net IDs are correctly assigned, then the Wilo-Smart Gateway automatically recog-
nises the connected devices. The Wilo-Smart Gateway then automatically starts
transferring the data from the connected devices to the Wilo-Smart Cloud.

NOTICE

If Stratos MAXO is a participant in the Gateway, ensure that the software version
of the Stratos MAXO is at least V 01.04.00.00 or higher. If the software version is
01.03.xx.xx or older, the pumps require a software update so that they can com-
municate with the Gateway via Wilo Net.

Summary of Contents for Wilo-Smart

Page 1: ...Pioneering for You Wilo Smart Gateway 2209950 Ed 02 2020 09 en Installation and operating instructions...

Page 2: ......

Page 3: ...LQ HUPDQ LOR 6 1RUWNLUFKHQVWU RUWPXQG HUPDQ Wilo Smart Gateway Art No 2197100 24 V DC SELV Imax 250mA Made in Germany WILO SE Wilopark 1 44263 Dortmund Germany LAN 1 ethernet LAN 2 ethernet USB RUN ST...

Page 4: ...Gateway Art No 2197100 24 V DC SELV Imax 250mA Made in Germany WILO SE Wilopark 1 44263 Dortmund Germany LAN 1 ethernet LAN 2 ethernet USB RUN STATUS digital I O Wilo Net 1 RS 485 Wilo Net 2 24V DC l1...

Page 5: ...rk 9 2 6 Unauthorised modification and manufacture of spare parts 9 2 7 Improper use 10 3 Transport inspection 10 4 Intended use 10 5 Product information 10 5 1 Type key 10 5 2 Technical data 10 5 3 S...

Page 6: ...en 6 WILO SE 2020 09 13 Appendix 21...

Page 7: ...ation which must be adhered to during installation and operation For this reason these installation and operating in structions must without fail be read by the installer and the responsible qualified...

Page 8: ...The operator must confirm and ensure the field of authority the competence and the monitoring of the personnel If the personnel do not possess the necessary know ledge they must be trained and instruc...

Page 9: ...ed physical sensory or mental capacities or lack of experience and knowledge if they are supervised or instructed on the safe use of the device and they understand the dangers that can occur Children...

Page 10: ...mage and completeness Where necessary make a complaint immediately CAUTION Damage due to incorrect handling during transport and stor age Protect the device from moisture frost and mechanical damage d...

Page 11: ...50 mA Electronics Electromagnetic compatibility EN 55032 Class B Interference resistance EN 61000 6 2 Emitted interference EN 61000 6 3 Degree of protection IP20 Protection class III Materials Housing...

Page 12: ...connection via the mobile network or WiFi Additional digital inputs and outputs are provided in case of future developments 6 3 User interface operation See Commissioning section 6 3 1 LED operating...

Page 13: ...rea after installation and electrical connection To this end install the Wilo Smart Gateway in a switch cabinet or distributor box WARNING Personal injury Adhere to existing accident prevention regula...

Page 14: ...ting the power supply 1 Strip 5 6 mm off the power supply s wire ends from the power supply unit 2 Connect the 24 V DC SELV power supply from the power supply unit 7 2 2 Terminal assignment Gateway co...

Page 15: ...ound LAN 1 Ethernet Local network interface Gateway configuration 10 100 MBit LAN 2 Ethernet WAN network interface Internet connection 10 100 MBit USB Will only be supported in future software version...

Page 16: ...o establish the Wilo Net connection the three H L GND terminals are wired with a communication cable from pump to pump to Gateway to pump Use shielded cables for cable lengths 2 m Up to 20 participant...

Page 17: ...be brought into an administrative network the following inform ation will help administrators to set up the network accordingly DNS service default setting can be changed 8 8 8 8 NTP service default s...

Page 18: ...ust be set so that the IP address is obtained via DHCP standard configuration The PC laptop is connected to the Gateway LAN 1 connection with a network cable patch cable RJ45 plug The Wilo Smart Gatew...

Page 19: ...ed MyWilo user is ideal for commissioning the Gateway If you have already used Wilo Smart connect with the Bluetooth connection this step is already completed During further commissioning the operator...

Page 20: ...electrical and electronic products Proper disposal and appropriate recycling of this product prevents damage to the en vironment and putting your personal health at risk NOTICE Disposal in domestic w...

Page 21: ...used can be sent on a data carrier by post Contact via e mail to wilo wilo com telephone call number 49 231 4102 0 or by post This offer is valid for a period of three years after the final delivery...

Page 22: ...RMIT TSERKL RUNG DECLARATION DE CONFORMITE UE CE We the manufacturer declare under our sole responsability that the products of the series Als Hersteller erkl ren wir unter unserer alleinigen Verantwo...

Page 23: ...anvendelsen af visse farlige stoffer 2011 65 UE 2015 863 2014 30 E 2011 65 UE 2015 863 2014 30 C 2011 65 UE 2015 863 WILO SE prohla uje e v robky uveden v tomto prohl en odpov daj ustanoven m n e uve...

Page 24: ...erklaring vermelde producten voldoen aan de bepalingen van de volgende Europese richtlijnen evenals aan de nationale wetgevingen waarin deze bepalingen zijn overgenomen WILO SE o wiadcza e produkty wy...

Page 25: ......

Page 26: ......

Page 27: ......

Page 28: ...Pioneering for You Local contact at www wilo com contact WILO SE Wilopark 1 44263 Dortmund Germany T 49 0 231 4102 0 T 49 0 231 4102 7363 wilo wilo com www wilo com...

Reviews: