Wilo Wilo-Rexa PRO-S Installation And Operating Instructions Manual Download Page 27

en

Installation and operating instructions • Wilo-Rexa PRO-S • Ed.01/2022-03

27

Maintenance work: trained sewage technology professional
Application/disposal of operating fluids used, basic engineering knowledge (installation/
dismantling)

9.2

Operator responsibilities

Provide the necessary protective equipment and make sure that the personnel wears it.

Collect operating fluids in suitable tanks and dispose of properly.

Dispose of protective clothing used in accordance with regulations.

Use only original parts of the manufacturer. The use of any non-original parts releases
the manufacturer from any liability.

Collect any leakage of fluid and operating fluid immediately and dispose of it according
to the locally applicable guidelines.

Provide the tools required.

If flammable solvents and cleaning agents are used, fire, naked flames and smoking are
prohibited.

Document maintenance tasks in the system’s inspection list.

9.3

Operating fluid

9.3.1

Oil types

ExxonMobile: Marcol 52

ExxonMobile: Marcol 82

Total: Finavestan A 80 B (NSF-H1 certified)

9.3.2

Filling quantities

The filling quantity depends on the motor power (see rating plate “P

2

”):

1.1 kW = 900 ml (30 US.fl.oz)

1.5 kW = 900 ml (30 US.fl.oz)

2.5 kW = 900 ml (30 US.fl.oz)

3.9 kW = 1500 ml (50.5 US.fl.oz)

5.0 kW = 1500 ml (50.5 US.fl.oz)

9.4

Maintenance intervals

Regularly carry out maintenance tasks.

Contractually adjust maintenance intervals depending on the actual environmental con-
ditions. Contact customer service.

If strong vibrations occur during operation, check the installation.

9.4.1

Maintenance intervals for normal
conditions

8000 operating hours or after 2 years

Visual inspection of the connection cables

Visual inspection of accessories

Visual inspection of the coating and housing

Function test of monitoring devices

Sealing chamber oil change

NOTICE! If a sealing chamber monitoring is installed, the oil

is changed according to the indicator!

5000 operating hours or after 10 years

Complete overhaul

9.4.2

Maintenance intervals for use in
sewage lifting units

When the pump is used in sewage lifting units inside buildings or on plots of land, carry out
maintenance intervals and measures in accordance with 

DIN EN 12056‑4

!

9.4.3

Maintenance intervals for harsh
conditions

Under the following operating conditions, shorten the specified maintenance intervals in
consultation with the customer service:

Fluids with long-fibre components

Turbulent inlet (e.g. due to air entry, cavitation)

Highly corrosive or abrasive fluids

Strongly gassing fluids

Operation at an unfavourable duty point

Pressure surges

If there are harsh operating conditions, it is recommended to conclude a maintenance con-
tract.

Summary of Contents for Wilo-Rexa PRO-S

Page 1: ...Pioneering for You Wilo Rexa PRO S 6092606 Ed 01 2022 03 en Installation and operating instructions...

Page 2: ...Rexa PRO S http qr wilo com 415 Rexa PRO https qr wilo com 772...

Page 3: ...xplosive atmosphere 14 5 6 Scope of delivery 14 5 7 Accessories 14 6 Installation and electrical connection 14 6 1 Personnel qualifications 14 6 2 Installation types 15 6 3 Operator responsibilities 1...

Page 4: ...cal inaccuracies and or omissions The illustrations used may differ from the ori ginal and are intended as an example representation of the device 1 5 Exclusion from warranty and liabil ity Wilo shall...

Page 5: ...serious injuries CAUTION Failure to follow the instructions can lead to property damage and a possible total loss NOTICE Useful information on handling the product Markups Prerequisite 1 Work step lis...

Page 6: ...g knowledge installation dismantling Lifting work trained specialist for the operation of lifting devices Lifting equipment lifting gear attachment points Children and persons with limited abilities P...

Page 7: ...e device Observe the technical information in these installation and op erating instructions as well as on the rating plate Earth the device Observe provisions for connection to the electrical switchi...

Page 8: ...llowing points Wear a safety helmet according to EN 397 Comply with local regulations on the use of lifting equipment The technically correct use of the lifting equipment is the oper ator s responsibi...

Page 9: ...ting parts can crush and sever limbs Open all gate valves in the inlet and pressure pipe Ensure minimum water submersion by using dry running pro tection Sound pressure level depends on several factor...

Page 10: ...n Consult a doctor immediately Do not induce vomiting 2 14 Operator responsibilities Provide installation and operating instructions in a language which the personnel can understand Make sure that the...

Page 11: ...3 Storage DANGER Danger due to fluids which are hazardous to health Danger of bacterial infection Disinfect the pump after removal Observe the specifications of the work regulations WARNING Risk of i...

Page 12: ...such as stones wood metal etc Fluids containing high quantities of abrasive contents e g sand gravel Intended use also includes compliance with this manual Any other use is regarded as non compliant...

Page 13: ...lume flow Q See rating plate Activation type AT Direct Fluid temperature t 3 40 C 37 104 F Fluid temperature short term 60 C 140 F for 3 min Protection class IP68 Insulation class Cl F optionally H Sp...

Page 14: ...be used in zone 0 ATEX approval The pumps are suitable for operation in potentially explosive atmospheres Device group II Category 2 zone 1 and zone 2 These pumps must not be used in zone 0 FM approva...

Page 15: ...bers and narrow rooms as well as work involving risk of fall ing are dangerous work Such work may not be carried out autonom ously Only carry out work with another person Wear protective equipment Obs...

Page 16: ...lowing requirements The connected pressure pipe is self supporting The pressure pipe must not be suppor ted by the suspension unit The pressure pipe must not be smaller than the pump s discharge conne...

Page 17: ...Secure the pump against moving and falling over Bolt the pump support foot to the floor 5 Lay the pressure hose and fasten it properly at the appropriate place e g drainage 6 Correctly route the conn...

Page 18: ...pencil electrode via an Ex approved evaluation relay with an intrinsically safe circuit Observe the further information in the explosion protection section for the electrical connection Mains connect...

Page 19: ...ustomer service 6 5 3 Connection of the single phase AC motor 1 motor U1 Z1 3 U2 4 Cr Z2 5 C S M 1 gn ye L N PE 1 2 6 3 4 gn ye 1 2 6 21 20 DK Fig 6 Connection diagram 1 motor Wire Designation Termina...

Page 20: ...ation on electrical accessory connection or possible special configurations Please refer to the order confirmation or configuration overview for details on the special config uration 6 5 5 1 Connectio...

Page 21: ...tion adjustment 6 5 6 1 Direct activation Full load Set the motor protection to the rated current according to the rating plate Partial load operation Set the motor protection to 5 above the current m...

Page 22: ...to flying sparks in the hydraulics The hydraulics must be completely filled with pumped fluid during oper ation If air cushions form in the hydraulics there is a risk of explosion due to sparking Prev...

Page 23: ...irm bearing surface Avoid sinking If the pump has fallen over place it upright again before activating it If the pump moves away screw the pump to the ground Pump with bare cable end The pump is switc...

Page 24: ...erating times with non immersed operation Longer operating time is possible if cooling of the motor is ensured S3 10 can be operated according to S3 25 S3 25 can be operated according to S3 50 CAUTION...

Page 25: ...arrying out electrical work can lead to death due to electric shock Electrical work must be carried out by a qualified electrician Observe local regulations DANGER Risk of fatal injury due to dangerou...

Page 26: ...not damage the connection cable Pay attention to the connection cable when setting down the pump 6 Thoroughly clean the pump see section Cleaning and disinfecting 8 4 3 Clean and disinfect Wear protec...

Page 27: ...0 ml 50 5 US fl oz 5 0 kW 1500 ml 50 5 US fl oz 9 4 Maintenance intervals Regularly carry out maintenance tasks Contractually adjust maintenance intervals depending on the actual environmental con dit...

Page 28: ...tics of the fluid Power consumption can provide an early indication of damage or malfunctions in the impeller bearings or motor which can be rectified Larger voltage fluctuations strain the motor wind...

Page 29: ...id under pressure High pressure can build up in the motor This pressure is released when the screw plugs are opened If screw plugs are opened without due caution they can be ejected at high speed Hot...

Page 30: ...bserve the work regulations Safety shoes Protection class S1 uvex 1 sport S1 Protective gloves 4X42C uvex C500 wet Safety goggles uvex skyguard NT For detailed marking of frame and disc see the sectio...

Page 31: ...Fit new cutting head 6 Wet fastening screw with thread locking fluid and screw it into cutting head Tighten the fastening screw hand tight 7 Secure the cutting head Insert wedge between cutting head a...

Page 32: ...trician 2 Increased power consumption due to major voltage drop Have the voltage of individual phases checked by a qualified electrician Contact the electricity distribution network 3 There are only t...

Page 33: ...djusted if necessary Fault The pump does not run smoothly and is noisy 1 Improper duty point Check the pump configuration and the duty point contact customer service 2 Hydraulics jammed Clean the hydr...

Page 34: ...ectrical and electronic products Proper disposal and appropriate recycling of this product prevents damage to the environ ment and putting your personal health at risk NOTICE Disposal in domestic wast...

Page 35: ...of 0 4 bar 6 psi is recommended Make sure that the pump operates without jerks and vibrations without oscillations reson ances pendulum torques across the entire control range Otherwise the mechanical...

Page 36: ...be equipped with a temperature controller 2 circuit temperature monitoring 13 3 3 Intended use IECEx certification The pumps are suitable for operation in potentially explosive atmospheres Device grou...

Page 37: ...f the low temperature threshold is reached CAUTION Motor damage due to overheating If automatic reactivation takes place comply with the specifications for max switching frequency and switching break...

Page 38: ...he potentially explosive area Only use pumps with the appropriate Ex rating within potentially explosive atmospheres Do not exceed the max fluid temperature Do not allow the pump to dry run The custom...

Page 39: ......

Page 40: ...Pioneering for You Local contact at www wilo com contact WILO SE Wilopark 1 44263 Dortmund Germany T 49 0 231 4102 0 T 49 0 231 4102 7363 wilo wilo com www wilo com...

Reviews: