16
WILO SE 11/2017
en
• Align the upper shut-off device laterally.
• When installing in the feed of open systems, the
safety supply must branch off upstream of the pump
(EN 12828).
• Complete all welding and brazing work.
• Flush the pipe system.
Rotating the
motor head
Rotate the motor head (2+5) before installing and con
-
necting the pump.
• If necessary, remove the thermal insulation shell.
• Hold the motor head (2+5) and unscrew the 4 housing
screws (4).
• Carefully rotate the motor head (2+5).
• Observe the permitted installation position (Fig. 2)
and the direction arrow on the pump housing (1).
• Tighten the 4 housing screws (4).
CAUTION!
Leaking water may damage the control module.
• Align the upper shut-off device such that leaking
water cannot drip onto the control module (5).
WARNING!
Risk of fatal injury from magnetic field!
Risk of fatal injury for people with medical implants due
to permanent magnets installed in the pump.
• Never remove the rotor.
1
2
4
5
CAUTION!
Damage to the inner gasket causes leakage.
• Carefully rotate the motor head (2+5) without
removing it from the pump housing (1).