Table 11: Error table
Additional explanations of
error codes
Error E021:
Error “E021” indicates that the pump requires more power than is
permitted. To ensure that the motor and electronic module do not
suffer irreparable damage, the drive protects itself by switching the
pump off if an overload lasts more than 1 minute.
The most common causes of this error are a pump that is configured
too small, especially when pumping viscous fluids, or an excessive
volume flow in the system.
When this error code is displayed, there is not an error in the electronic
module.
Error E070; possibly combined with error E073:
If additional signal lines or control cables are connected to the elec-
tronic module, the effects of EMC (immission / interference resist-
ance) may interrupt communication. This results in error code “E070”
being displayed.
You can check this by disconnecting all the communication lines
installed by the customer from the electronic module. If the fault no
longer occurs, there could be an external signal interfering on the
communication line(s) that exceeds the applicable standard values.
The pump can only return to normal operation once the source of
interference is remedied.
11.3
Acknowledge fault
General
In the event of a fault, the error page is displayed instead of the status
page.
In this case, the following procedure can generally be used for naviga-
tion (Fig. 45):
• To change to the menu mode, press the operating button.
Menu number <6.0.0.0> flashes on the display.
By turning the operating button, it is possible to navigate in the menu
as usual.
E111
Excess current
Internal electronics error
Request customer service
B
A
E112
Excess rotation
speed
Internal electronics error
Request customer service
B
A
E121
Motor PTC short-
circuit
Internal electronics error
Request customer service
A
A
E122
Interruption to NTC
power element
Internal electronics error
Request customer service
A
A
E124
Interruption to NTC
electronic module
Internal electronics error
Request customer service
A
A
Impermissible
combinatorics
E099
Pump type
Different pump types
have been
interconnected
Request customer service
A
A
System errors
E119
Turbine operation
error (flow against
flow direction; pump
cannot start)
The flow is driving the
pump impeller; electrical
current is being fed back
to the mains.
Check the setting, check
system for proper operation
Caution!
Prolonged operation
can cause damage to the
electronic module.
A
A
Classification
No.
Error
Cause
Remedy
Error type
HV
AC
Fig. 45: Navigation in the event of an error
6.0.0.0
6.0.0.0
1/1 S
10
E000
5.0.0.0
E000