Installation and operating instructions • Wilo-Rexa MINI3 • Ed.03/2022-05

9

3.

Slide the pressure hose onto the hose connection at the pres-
sure port.

4.

Secure the pressure hose to the hose connection using the
hose clip.

5.

Position the pump at the installation site.

CAUTION! Use a hard surface or underlay at the installation
site to prevent sinking on soft substrate.

6.

Lay the pressure hose and fasten it in the appropriate place
(e.g. drainage). 

CAUTION! If the pump is placed in a full

chamber, hold the pump at a slight angle when immersing.
This causes the air to escape from the pump!

7.

Route the connection cable to the socket/power supply.

Pump is installed.

5.3

Electrical connection

Mains connection with correctly installed protective earth con-
ductor.

Residual-current device (RCD) is installed with 30 mA.

Mains connection fuse protection: max. 16 A.

Voltage (U) and frequency (f) data on the rating plate corres-
pond to the data of the mains connection.

Do 

not

 connect the pump if:

The connection cable is damaged
Have the connection cable replaced by a qualified electrician or
the customer service.

A standalone inverter is in use
Stand-alone inverters are used in autonomous power supplies,
e.g. solar power supply, and can generate overvoltages. Over-
voltages can destroy the pump.

A multiple plug socket or power strip is in use

An energy-saving plug is in use
This reduces the energy supply to the pump and the pump may
heat up too much.

Operation on start-up controls
The pump is not suitable for operation on a frequency converter
or a soft start control.

Explosive atmospheres
Do not connect and operate the pump inside potentially ex-
plosive atmospheres!

5.3.1

Connection: Pump with plug

Provide for a socket (type E or type F) with earthing contact. To
connect the pump, insert the plug into the socket.

NOTICE

Pump starts up or is ready for operation!

Once the plug is connected to the socket, the pump
will either start immediately or be ready for opera-
tion:

• Pump 

without float switch

: pump switches on

immediately!

• Pump 

with float switch

: pump is ready for oper-

ation and will switch on depending on the fill
level!

We recommend switching the socket on and
off using a separate main switch!

5.3.2

Connection: Pump without a plug

DANGER

Risk of fatal injury due to electrical current!

Improper conduct when carrying out electrical work
can lead to death due to electric shock!

• Electrical work must be carried out by a qualified

electrician!

• Observe local regulations!

CAUTION

Irreparable damage as a result of water pen-
etration

Connection cables without plugs feature bare cable
ends. Water may penetrate the connection cable
and pump via these bare cable ends. This will des-
troy both the connection cable and the pump. Never
immerse the bare end of the connection cable in
fluid. Firmly seal it during storage.

The pump has a connection cable with bare cable end. The pump
must be permanently connected to a switchgear. Observe the fol-
lowing points:

Earth the device properly!

Provide a motor protection switch!
The minimum requirement is a thermal relay/motor protection
switch with temperature compensation, differential trip and re-
activation lock according to local regulations.

Install the mains disconnection device!
Minimum requirement: Main switch with all-pole disconnection.

Pump with single-phase AC motor

To connect the pump firmly to the switchgear, cut off the plug.
Carry out connection to a switchgear as follows:

Wire colour

Terminal in switchgear

Brown (bn)

L (phase)

Blue (bl)

N (neutral conductor)

Green/yellow (gn-ye)

Earth (protective earth con-
ductor)

Pump with three-phase AC motor

The pump is suitable for connection to a clockwise rotating field.
Check the rotating field with a rotating-field-testing device before
connection and correct if necessary. 

CAUTION! The pump is not

approved for operation with a counter-clockwise rotating field!

Carry out connection to a switchgear as follows:

Wire colour

Terminal in switchgear

Brown (bn)

U

Black (bk)

V

Blue (bl)

W

Green/yellow (gn-ye)

Earth (protective earth con-
ductor)

Adjust the motor protection

Set the motor protection switch to the rated current (see rating
plate).

Summary of Contents for Rexa MINI3

Page 1: ...Pioneering for You Wilo Rexa MINI3 3094116 Ed 03 2022 05 en Installation and operating instructions...

Page 2: ...Rexa MINI3 https qr wilo com 405...

Page 3: ...6 2 3 Type key 7 2 4 Scope of delivery 7 2 5 Functions 7 3 Application use 7 3 1 Intended use 7 3 2 Improper use 7 4 Transport and storage 8 5 Installation and electrical connection 8 5 1 Installatio...

Page 4: ...in grey Damage to property Safety instructions start with a signal word and are displayed without a symbol Signal words DANGER Failure to follow the instructions will result in serious injuries or dea...

Page 5: ...change Wear a breathing protection mask e g Half mask 3M series 6000 with filter 6055 A2 1 9 Electrical connection Do not connect products with a damaged connection cable Have the connection cable rep...

Page 6: ...installation in intermittent operation 1 2 3 4 5 6 Fig 1 Overview 1 Handle 2 Motor housing 3 Discharge connection 4 Pump housing 5 Float switch 6 Connection cable Rexa MINI3 V P Sewage pump with vort...

Page 7: ...e motor becomes too hot the pump is deactivated After the motor has cooled down the pump is automatically switched on again 2 5 2 Float switch The Rexa MINI3 V A is equipped with a float switch The fl...

Page 8: ...dis charge connection Seal pipe connections with Teflon tape Install all specified valves in accordance with local requirements gate valve non return valve Lay the discharge pipe frost proof Air pocke...

Page 9: ...ion Pump without float switch pump switches on immediately Pump with float switch pump is ready for oper ation and will switch on depending on the fill level We recommend switching the socket on and o...

Page 10: ...pump cycles 1 Flood the pump chamber Open inlet NOTICE The required feed quantity for the test run can also be simulated using another water source 2 When the switch on level is reached pump starts 3...

Page 11: ...mp has been cleaned Pack and store the pump NOTICE If the suction port is very contaminated remove the cover plate for thorough cleaning 8 2 Cleaning the pump interior WARNING Sharp edges on the impel...

Page 12: ...n port strainer silted clogged Shut down the pump remove it and clean it 5 Air in the pump pressure pipe Position the pump at a slight angle to allow air to escape Install a bleed unit in the pressure...

Page 13: ...G Risk of environmental and health damage due to incorrect disposal of oils Oil is harmful to health and the environment Do not dispose of oil with domestic waste or in the sewage system Collect the o...