Description
en
Installation and operating instructions Wilo-RAIN3
35
Menu no.
Parameter /
info
Min.
Max. Text
Default
Unit
Ac-
cess
level
Description
5.51
Over flow on
threshold
cistern
1
1000
100
cm
3
The level threshold in cistern above over-
flow is reported. 5.22 < 5.51 < 5.24 <
5.29
5.52
Tap water
on threshold
cistern
1
1000
<5.22> +10
cm
2
The level threshold below which to
switch to TWM (distance refer to 5.22)
5.22 < 5.52 < 5.53 < 5.51
5.53
Rain water
on threshold
cistern
1
1000
<5.22> +10
cm
2
The level threshold above which to
switch to RWM (distance refer to 5.52)
5.22 < 5.52 < 5.53 < 5.51
5.54
Calcination
protection
0
7
7
d
2
To protected the valve against calcina-
tion it can be operate from time to time
as defined in this parameter
5.55
System
flushing
7
31
7
d
2
To clean up the break tank once in a
while it can be flushed with fresh water
after period defined here
5.56
Flushing
duration
1
9
3
min
2
Time which pump has to run totally in
TWM for the next pump operations. After
this time RWM are possible again.
5.57
Max. run-
ning time
pump
0
360
0
min
2
Pump should no longer run than the
timespan defined here or else an alarm is
generated; 0s means unlimited running
time and no alarm message
5.59
Fault mes-
sage beha-
vior
Raise - Fall
Fall
2
zero- or one-signal in case of failure
5.61
Minimum
pressure
0.7
1.0
1.0
bar
2
The pressure threshold below which a dry
running is detected
5.62
Delay dry
run protec-
tion
1
180
15
s
2
The delay to detect dry run. It avoids false
dry run detection by short impulse on the
input
5.63
Dry run tap
water mode
duration
1
180
20
s
2
Time in TWM to build up minimum pres-
sure
5.64
Dry run rain
water mode
duration
1
180
30
s
2
Time in RWM to build up minimum pres-
sure
5.70
Maximum
pump cycles
per hour
1
60
35
1/h
2
Raise an alarm when pump is starting
more frequently than that threshold
Menu no.
Parameter /
info
Min.
Max. Text
Default
Unit
Ac-
cess
level
Description
6.00
Alarm
1
The submenu contains the ten most re-
cent error codes for alarms that have ap-
peared in the panel during operation
6.01
Quit alarm
Off - Reset
OFF
1
Use this item to reset all acknowledge-
able alarms
6.02
Alarm his-
tory 0 (new-
est item)
0
2550
0
1
The most recent error code
6.03
Alarm his-
tory 1
0
2550
0
1
The second most recent error code
6.04
Alarm his-
tory 2
0
2550
0
1
The third most recent error code
6.05
Alarm his-
tory 3
0
2550
0
1
Summary of Contents for RAIN 3-25 EM
Page 2: ...Fig 1 Fig 3 Fig 2 52 Rp 3 4 Rp 1 52...
Page 3: ...Fig 4...
Page 4: ...Fig 5 Fig 6 Fig 7 Fig 9 Fig 10 Fig 8...
Page 5: ...Fig 11 Fig 12 Max 5 N m Max 5 N m...
Page 6: ......
Page 7: ...7 Deutsch 8 English 26 Fran ais 44 Nederlands 64 esky 83...
Page 104: ......
Page 105: ......
Page 106: ......