Installation and operating instructions Wilo-Control SC-Fire Jockey

13

• The type of mains, current and voltage of the 

mains connection must match the details on the 
rating plate of the control device.

NOTE:

• Fuse on mains side in accordance with the infor-

mation in the wiring diagram

• Feed the ends of the mains cable through the 

threaded cable connections and cable inlets and 
wire them according to the markings on the ter-
minal strips.

• Earth the pump/installation in accordance with 

the regulations.

7.2.1 Power supply connection

Connect the on-site 4-wire cable (L1, L2, L3, PE) 
for the supplying network to the main switch, in 
accordance with the circuit diagram.

7.2.2 Pump connection

Observe the installation and operating instruc-
tions for the pumps!

The pump is connected to the terminal strips as 
per the circuit diagram. The pump is operated via 
direct starting.

7.2.3 Pressure switch connection

The pressure switch is connected to the terminal 
strips as per the circuit diagram. The pressure 
switch contact closes when there is a pressure 
drop and switches on the pump.

7.2.4 Fault signal connection

At the fault signal terminal strip, a signal indicating 
a fault can be transferred to a potential-free con-
tact (see circuit diagram).

8 Commissioning

WARNING! Risk of fatal injury! 
Commissioning by qualified personnel only! 
Improper commissioning poses a risk of fatal 
injury. Have commissioning performed by quali-
fied personnel only.

DANGER! Risk of fatal injury!
When working on the open switchgear, there's a 
danger of electric shock from touching the live 
components. 
This work must only be carried out by qualified 
personnel!

It is recommended that you have the switchgear 
commissioned by Wilo customer service.

Before switching on for the first time, the on-site 
wiring must be checked, in particular the earthing.

Tighten all connection terminals prior to com-
missioning!

8.1 Checking the motor direction of rotation

By briefly switching on the pump in “manual” 
operating mode (see 6.2.3), check that the direc-
tion of rotation of the pump in mains operation is 
correct. When the pump motor runs out, compare 
the direction of rotation of the fan wheel and the 
direction specified on the pump housing.
If the direction of rotation of the pump in mains 
operation is wrong, swap over any two phases of 
the power cable.

8.2 Setting the excess current protection

In the case of direct starting, the motor protection 
switch must be set to rated current I

N

 for the 

pump. The rated current I

N

 is specified on the 

pump's rating plate.

9 Maintenance

Have maintenance and repair work carried out 
by qualified skilled personnel only!
DANGER! Risk of fatal injury!
There is a risk of fatal injury from electric shock 
when working on electrical equipment.

• The switchgear should be electrically isolated 

and secured against unauthorised switch-on 
during any maintenance or repair work.

• Any damage to the connection cable should only 

ever be eradicated by a qualified electrician.

• The switchgear must be kept clean.
• Visual inspection of the electric system parts in 

the switchgear.

10 Faults, causes and remedies

DANGER! Risk of fatal injury!
There is a risk of fatal injury from electric shock 
when working on electrical equipment.
Have faults remedied by qualified skilled per-
sonnel only! Follow the safety instructions in 
Section 2 Safety.
Before all work to remedy faults, disconnect the 
unit from the power supply, and make sure it 
cannot be switched back on by unauthorised 
persons.

Summary of Contents for Control SC-Fire Jockey

Page 1: ...Fire Jockey Pioneering for You 2 541 363 Ed 01 2014 02 Wilo de Einbau und Betriebsanleitung en Installation and operating instructions fr Notice de montage et de mise en service nl Inbouw en bedienin...

Page 2: ...Fig 1 I ON 0 OFF...

Page 3: ...information is disregarded CAUTION There is a risk of damaging the pump unit Caution implies that damage to the product is likely if this information is disregarded NOTE Useful information on handling...

Page 4: ...manufacture of spare parts will impair the safety of the product personnel and will make void the manufacturer s declarations regarding safety Modifications to the product are only permissible after...

Page 5: ...f by the control depending on the pressure The system s operating statuses e g standby pump operation and fault are dis played visually by LEDs on the door In addition the operating mode can be change...

Page 6: ...of the pressure switch or pressure The pump remains continuously switched on for as long as the rotary switch is set to manual 6 2 4 Switchgear display elements Operational standby The operational st...

Page 7: ...t is recommended that you have the switchgear commissioned by Wilo customer service Before switching on for the first time the on site wiring must be checked in particular the earthing Tighten all con...

Page 8: ...ellow The fault signal can be transferred to the potential free contact Faults Causes Remedy Signal lamp is lit up yellow Excess current protection device has tripped Switch the motor protection switc...

Page 9: ......

Page 10: ...Pioneering for You WILO SE Nortkirchenstra e 100 D 44263 Dortmund Germany T 49 0 231 4102 0 F 49 0 231 4102 7363 wilo wilo com www wilo com...

Reviews: