background image

30

Part Number 550-142-785/0812 

  

GWI

 Series 2 

Gas-Fired Water Boilers – 

Boiler Manual

❏ 

Check/test

❏ 

Review with owner

1.  Review the User’s Information Manual with the owner.
2.  Emphasize the need to perform the maintenance schedule 

specified in the User’s Information Manual (and in this manual 

as well).

3.  Remind the owner of the need to call in a licensed contractor 

should the boiler or system exhibit any unusual behavior.

4.  Remind the owner to follow the proper shutdown procedure 

and to schedule an annual start-up at the beginning of the 

next heating season.

1.  Shut down boiler:

•  Follow “To Turn Off Gas to Appliance” instructions on boiler 

and “Operating instructions”.

•  Do not drain boiler unless it will be exposed to freezing 

temperatures. If using antifreeze in system, do not drain.

2.  Follow shutdown procedure.

3.  Remove venting system connection to boiler.

4.  Remove top jacket panel. Turn back insulation.
5.  Remove collector box/transition assembly. Clean sealant from 

assembly and sections.

6.  Remove radiation plates hanging between sections.

7.  Remove burners from base. Brush and vacuum burners to 

remove all dust and lint. Verify that all burner ports are free of 

debris.

8.  Place newspapers in base of boiler to collect soot.
9.  Clean between sections with wire flue brush.

10. Remove newspaper and soot. Vacuum or brush base and 

surrounding area.

11. Reinstall radiation plates.

12. Replace collector box/transition assembly. Seal with sealant. 

Obtain gas-tight seal to prevent flue gas spillage and carbon 

monoxide  emissions,  resulting  in  severe  personal  injury  or 

death. 

13. Replace insulation and jacket top panel.
14. Start up boiler following 

pages 18 –20

 of this manual and the 

boiler “Operating  Instructions”.  Excessive  sooting  indicates 

improper gas combustion. If found check for proper combus

-

tion and make any necessary adjustments.

❏ 

Cleaning boiler heating surfaces

Boiler relief valve

1.  Inspect the relief valve and lift the lever to verify flow as in the 

following  warnings,  excerpted  from  a  relief  valve  manufac

-

turer’s warning label. Before operating any relief valve, ensure 

that it is piped with its discharge in a safe area to avoid severe 

scald potential. Read manual Section 4, page 13

,  before 

proceeding further.

  Safety relief valves should be reinspected AT LEAST 

ONCE  EVERY  THREE YEARS,  by  a  licensed 

plumbing contractor or authorized inspection 
agency, to ensure that the product has not been 

affected  by  corrosive  water  conditions  and  to 

ensure that the valve and discharge line have not 

been  altered  or  tampered  with  illegally.  Certain 

naturally occurring conditions may corrode the valve 
or its components over time, rendering the valve 
inoperative. Such conditions are not detectable 
unless the valve and its components are physically 
removed and inspected. This inspection must 
only be conducted by a  plumbing contractor or 
authorized inspection agency — not by the owner. 

Failure to reinspect the boiler relief valve as directed 

could result in unsafe pressure buildup, which can 

result in severe personal injury, death or substantial 
property damage.

2.  After following the above warning directions, if the relief valve 

weeps or will not seat properly, replace the relief valve. Ensure 

that the reason for relief valve weeping is the valve and not 

over-pressurization  of  the  system  due  to  expansion  tank 

waterlogging or undersizing.

  Following installation, the valve lever must be op-

erated  AT  LEAST  ONCE  A YEAR  to  ensure  that 

waterways  are  clear.  Certain  naturally  occurring 

mineral deposits may adhere to the valve, rendering 
it inoperative. When manually operating the lever, 

water will discharge and precautions must be taken 

to avoid contact with hot water and to avoid water 

damage. Before operating lever, check to see that 

a discharge line is connected to this valve direct-

ing the flow of hot water from the valve to a proper 

place of disposal otherwise severe personal injury 

may result. If no water flows, valve is inoperative. 

Shut down boiler until a new relief valve has been 

installed.

  The boiler contains ceramic fiber and fiberglass 

materials. Use care when handling these materials 

per instructions on page 48

 of this manual. Failure 

to comply could result in severe personal injury.

11  Service and maintenance 

continued

Summary of Contents for GWI-047

Page 1: ...lation when determining boiler location Any claims for damage or shortage in shipment must be filed immediately against the transporta tion company by the consignee USER Please read the following Fail...

Page 2: ...erheating occur or gas supply fail to shut off do not turn off or disconnect electrical supply to circulator Instead shut off the gas supply at a location external to the appliance 5 Do not use this b...

Page 3: ...imum clearance to combustible materials 1 Hot water pipes must be at least from combustible material 2 Single wall vent pipe must be at least 2 inches from combus tible material 3 Type B double wall m...

Page 4: ...isted vent cap must extend at least 3 feet above the highest point where it passes through a roof of a building and at least 2 feet higher than any portion of a building within a horizontal distance o...

Page 5: ...e personal injury or death check for products or areas listed below before installing boiler If any of these contaminants are found remove contaminants permanently OR isolate boiler and provide outsid...

Page 6: ...ed air dampers If the air openings are fitted with motorized dampers electrically interlock the damper to Prevent the boiler from firing if the damper is not fully open Shut the boiler down should the...

Page 7: ...at once Failure to do so can damage boiler resulting in substantial property damage Do not use petroleum based cleaning or sealing compounds in boiler system Severe damage to boiler will occur resulti...

Page 8: ...tallation Code 2 To prevent downdrafts chimney should extend at least 3 feet above the highest point where it passes through a roof and at least 2 feet higher than any portion of a building within a h...

Page 9: ...elbows Do not exceed data in Table 4 4 Select vent components from separate GWI Vent Component Supplement All components including the vent starter must be of the same vent manufacturer Do not mix co...

Page 10: ...149 1 or B149 2 Installation Code Terminate vent no less than 6 feet from another com bustion air inlet 3 feet from any other building opening and 3 feet from any gas service regulator 13 See Figures...

Page 11: ...integral screen Elbow and termination coupling with screen not available for StaR 34 6 Do not seal vent pipe slip connector for Saf T Vent to inside or outside plate 7 If passing through noncombustibl...

Page 12: ...ual Using any termination other than one of those shown could cause nuisance outages and loss of heat resulting in substantial property damage Direct exhaust venting continued Figure 8 Sidewall vent t...

Page 13: ...ould result in failure of the relief valve to operate result ing in possibility of severe personal injury death or substantial property damage Test the operation of the valve after filling and pres su...

Page 14: ...tallation and Piping Guides If boiler is connected to heating coils located in air handling units where they can be exposed to refrigerated air use flow control valves or other au tomatic means to pre...

Page 15: ...nough to allow temperatures to level off It takes a while for the boiler water temperature to rise as the flow changes 3 Bypass valve 2 allows hot boiler outlet water to blend with colder return water...

Page 16: ...ath or substantial property damage 5 Use pipe dope compatible with propane gases Apply sparingly only to male threads of pipe joints so that pipe dope does not block gas flow 5 Install gas piping Fail...

Page 17: ...ments of equipment con nected to it If connected directly to boiler seeWiring diagrams 6 Field wiring page 24 and 25 for anticipator setting For other devices see manufacturer s specifications Wiring...

Page 18: ...rop Added water will dilute the antifreeze reducing the freeze protection level Preparation Fill the system with water 1 Close manual and automatic air vents and boiler drain cock 2 Fill to correct sy...

Page 19: ...gy by reducing the boiler water temperature as the heating load decreases This feature is equipped with an override which is provided primarily to permit the use of an external energy management syste...

Page 20: ...ff gas valve Manometer should confirm there is no gas flow Pilot will relight flame sensing element will sense pilot flame and main burners reignite Set limit control s to system temperature requireme...

Page 21: ...ADJUST In the MIN position the time delay is zero and the IMPORTANT notice below must be observed IMPORTANT In accordance with Section 325 f 3 of the Energy Policy and Conservation Act this boiler is...

Page 22: ...es light and control module senses flame cur rent spark generator is turned off and main valve opens c Natural Gas If pilot does not light within 15 seconds pilot valve is closed and spark generator i...

Page 23: ...23 Part Number 550 142 785 0812 GWI Series 2 Gas Fired Water Boilers Boiler Manual Figure 18 Control module sequence of operation status light indications 9a Sequence of operation...

Page 24: ...24 Part Number 550 142 785 0812 GWI Series 2 Gas Fired Water Boilers Boiler Manual 9a Sequence of operation continued Figure 19 Schematic wiring diagram...

Page 25: ...25 Part Number 550 142 785 0812 GWI Series 2 Gas Fired Water Boilers Boiler Manual Figure 20 Ladder wiring diagram 9a Sequence of operation continued...

Page 26: ...upplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire depart ment What to do if you smell gas 1 Stop Read the safety information ab...

Page 27: ...e could result in severe personal injury death or substantial property damage Service technician see following pages for instructions Owner maintenance see User s Information Manual for instructions A...

Page 28: ...Severe damage to boiler will occur resulting in substantial property damage Eliminate all system or boiler leaks Continual fresh makeup water will reduce boiler life Minerals can build up in sections...

Page 29: ...valve seat 4 Replace cap by twisting all the way onto valve and then un screwing one turn Limit controls and cutoffs 1 Inspect and test the boiler limit control Verify operation by turn ing control se...

Page 30: ...ning label Before operating any relief valve ensure that it is piped with its discharge in a safe area to avoid severe scald potential Read manual Section 4 page 13 before proceeding further Safety re...

Page 31: ...check pressure switch setting if specified in Troubleshooting charts Make sure boiler water temperature is 100 F or cooler before starting procedure to obtain appropri ate readings 1 See Figure 21 an...

Page 32: ...d 20 seconds OR ignition control will automatically restart sequence of operation after 1 hour waiting period INDICATOR LIGHT CONDITION POWER TSTAT CIRC High voltage detected on TSTAT circuit POWER PU...

Page 33: ...33 Part Number 550 142 785 0812 GWI Series 2 Gas Fired Water Boilers Boiler Manual Figure 23 Control module connections 12 Troubleshooting components continued...

Page 34: ...4 PURGE light flashing FLAME light flashing For insufficient heat or no heat problem go to Chart 7 if POWER light is on steady with no other light flashing No Yes On steady not flashing No Yes Usuall...

Page 35: ...the boiler thermostat leads two black low voltage leads in J box Connect a voltmeter across these two incoming wires Close each thermostat zone valve and relay in the external circuit one at a time an...

Page 36: ...lace if necessary Retest Try reseating plug in module receptacle and restart If inducer still does not work replace inducer assembly Retest No Yes Wait 45 seconds Does inducer motor operate No Yes Rem...

Page 37: ...ower to boiler Restart boiler following Operating instructions in this manual Section 10 Do FLAME and POWER lights still flash Boiler should now operate normally Original flashing FLAME light caused b...

Page 38: ...e ohmmeter indicate the switch is closed Inspect and check wire harness from control module to pressure switch Reseat connector in control module receptacle If harness is intact and properly seated bu...

Page 39: ...vice switch or breaker Check flame signal Detach sense lead from ignition control Figure 23 item 8 page 33 Connect negative lead of MICROAMMETER to control sense terminal Figure 23 item 8 page 33 Conn...

Page 40: ...normal sequence of operation Figure 18 page 23 If you have less than sufficient heat Is vent piping free of blockage No Yes Correct conditions and recheck operation See Figure 30 page 38 for normal s...

Page 41: ...t 460 003 700WT 2 Collector hood and transition assembly GWI 047 GWI 063 GWI 095 GWI 127 GWI 158 GWI 190 381 354 581WT 381 354 582WT 381 354 583WT 381 354 584WT 381 354 585WT 381 354 586WT 3 Temperatu...

Page 42: ...ss tie assembly in Base assembly 4 Access panel in Base assembly 5 Base pan angle left side in Base assembly 6 Base pan angle right side in Base assembly 7 Base pan in Base assembly 8 Burner rest in B...

Page 43: ...embly 13 Replacement parts continued The boiler contains ceramic fiber and fiberglass materials Use care when handling these materials per instructions on page 48 of this manual Failure to comply coul...

Page 44: ...10 408 05 335 511 546 924WT 2 Combination pressure temperature gauge with 2 short shank Ametek ENFM PTA 1088 4104 510 218 099WT 3 Drain valve Fittings shown are included with boiler Conbraco Hammond V...

Page 45: ...355WT 3 Natural gas Pilot assembly kit with orifice and aluminum pilot gas tubing All 511 330 166WT 3 Propane gas Pilot assembly kit with orifice and aluminum pilot gas tubing All 511 330 211WT 4 Cont...

Page 46: ...nsions Boiler model number Supply tapping inches NPT Return tapping inches NPT Gas connection size Note 3 inches NPT Gas manifold size Note 3 inches NPT W Jacket width inches GWI 047 1 10 GWI 063 1 1...

Page 47: ...pplica tions Install GWI boilers for residential radiant panel systems converted gravity heating systems or other low water temperature applications per instruc tions in this manual to avoid damage du...

Page 48: ...it in a plastic bag for disposal Wash potentially contaminated clothes separately from other clothing Rinse clothes washer thoroughly NIOSH stated First Aid Eye Irrigate immediately Breathing Fresh a...

Reviews: