background image

4

201843

DIRECT-VENT PROPANE/LP GAS HEATER

THE COMFORT PRODUCTS PEOPLE

6" Minimum

Adjacent

Side
Wall

Ceiling

Finished Floor, Carpet, Tile, etc.

12"

Minimum

12" Minimum

Figure 1 - Mounting Clearances as Viewed
from Front of Furnace

The clearance between the cabinet and the
wall it passes through is 0 inches.

Provide the following minimum clearances
from furnace cabinet (portion of cabinet
extending into outside air, as viewed from
the rear of furnace) to obstructions:

Cabinet Back: 36 inches

Cabinet Sides: 6 inches

Cabinet Bottom: Must be high enough
off the ground to prevent snow, water,
leaves, or any other objects from block-
ing vents.

Minimum Clearances

Provide the following minimum clearances
from furnace front cover to combustibles
(as viewed from the front of furnace, see
Figure 1):

Below Front Cover: 6 inches
Above Front Cover: 12 inches
Adjoining Wall: 12 inches
Front: 8 feet

 WARNING: Due to high tem-

peratures, never install the furnace:

• in an inside wall
• in a recreation vehicle
• in a window recessed in a thick

wall (creating an alcove)

• in an alcove
• behind a door or where an open

door would block normal air flow

• as a fireplace insert
• in high traffic areas
• near furniture or draperies
• in windy or drafty areas

 CAUTION: If you install the

furnace in a home garage, locate
furnace where moving vehicle will
not hit it.

For convenience and efficiency, install furnace:

• where there is easy access for operation,

inspection, and service

• in a central location, near an electrical

outlet

• where there is adequate clearance around

vents outside

Before installing furnace, inspect the wall,
floor, and outside areas. Make sure there are
no pipes, wiring, or anything else that would
interfere with furnace installation. If you are
installing thermostat in a wall, make sure
there are no pipes or wiring in the hollow
wall above the furnace. The thermostat wires
will pass through this wall from the attic.

Mounting hardware needed to mount fur-
nace into wall is included with the furnace.
No venting material is needed. You must
furnish tools and all gas piping from the gas
source to the furnace inlet.

INSTALLATION

 WARNING: A qualified ser-

vice person must install furnace.
Have service person inspect fur-
nace before use and at least an-
nually. Follow all local codes.

CHECK GAS TYPE

Use only  propane/LP gas. If your gas sup-
ply is not  propane/LP gas, do not install
furnace. Call dealer where you bought fur-
nace for proper type furnace.

INSTALLATION ITEMS

Before installing furnace, make sure you
have all items below:

• electric drill

• drill bits

• Phillips screwdriver

• hammer

• pipe wrench

• stud locator or small finishing nails

• equipment shutoff valve (supplied)

• test gauge connection (see Figure 15,

page 10)

• piping (check local codes)

• sealant (resistant to propane/LP gas)

• ground joint union

• sediment trap

• tee joint

LOCATING FURNACE

This furnace is designed to be mounted in a
wall that is 4 to 18 inches thick. You can also
mount furnace in a window.

 WARNING: Do not install fur-

nace in interior wall of building. You
must install furnace in exterior wall
of building. Rear of furnace must
extend into open, outside air. This
lets poisonous exhaust gases ven-
tilate to the outdoors.

 WARNING: Maintain the mini-

mum clearances shown in Figure
1. If you can, provide greater clear-
ances from floor, ceiling, and
joining wall.

 WARNING: Turn off electrical

circuits that pass through the wall
where you are going to install the
furnace.

NOTICE: This furnace must be
electrically grounded. Follow all
local codes. In the absence of
local codes, follow the 

National

Electric Code, ANS/NFPA 70
(U.S.) or Canadian Electrical Code
Part I-CSA C22.1 (Canada).

Summary of Contents for 2503531

Page 1: ...tion adjustment alteration service or maintenance can cause injury or property dam age Refertothismanual for correct installation and operational proce dures Forassistanceor additional information con...

Page 2: ...s Propane LP gas is odor less An odor making agent is added to pro pane LP gas The odor helps you detect a propane LPgasleak However theodoradded to propane LP gas can fade Propane LP gas may be prese...

Page 3: ...65 98 For purposes of input adjustment SPECIFICATIONS Install and use furnace with care Follow all localcodes Intheabsenceoflocalcodes use the latest edition of the following National Fuel Gas Code AN...

Page 4: ...Ifyouare installing thermostat in a wall make sure there are no pipes or wiring in the hollow wallabovethefurnace Thethermostatwires will pass through this wall from the attic Mounting hardware neede...

Page 5: ...000 BTU Hr Model Use a proper sized drill bit Drill holes through wall and into studs at marked locations 40 000 BTU Hr Model Use a proper sized drill bit On wall stud side of opening drill holes thro...

Page 6: ...r anything else that would interfere with install ing thermostat Do not mount thermo stat to stud If there are any obstruc tions choose a new location 3 Provide two 18 gauge insulated stranded wires f...

Page 7: ...t Wires to Thermostat Wall Anchors CAUTION Use only new black iron or steel pipe Copper tubing may be acceptable in cer tain areas Check local codes Use pipe large enough in diam eter to allow proper...

Page 8: ...plug 9 Slide furnace back into furnace cabi net Make sure exhaust tube gaskets are in place Make sure exhaust and intake vent tubes extend into vent caps on back of cabinet Replace two screws by exhau...

Page 9: ...0 BTU Hr 15 000 BTU Hr for other gas appliances 55 000 BTU Hr total 55 000 2500 22 Locate 22 or higher on chart below According to the chart below you should use 40 feet or less of 3 8 pipe 125 feet o...

Page 10: ...Figure 15 CAUTION Usepipejointseal ant that is resistant to liquid pe troleum LP gas Slab Floor Installation Equipment Shutoff Valve Test Gauge Connection To Gas Supply 3 Min Sediment Trap Gas Piping...

Page 11: ...0 cycle grounded outlet at furnace location 2 The furnace has a three pronged grounded plug Use only a grounded three prong outlet IMPORTANT Some local codes require rigid or semi rigid conduit or met...

Page 12: ...e burner Do not try to light the burner by hand 8 Plug in furnace 9 Set thermostat to desired setting If thermostat is set above room tem perature the blower will come on 10 Allow approximately 45 sec...

Page 13: ...forces the combus tion products out of the exhaust tube s The Combustion air blower is sealed so that air does not pass between it and the circulating room air blower 3 When the blower motor reaches...

Page 14: ...p and water mixture Wipe cabinet and front cover to remove dust Use a vacuum cleaner to remove dust from front cover louvers EXHAUST AND INTAKE VENTS Make sure the exhaust and intake vents are not blo...

Page 15: ...h is sailing in far enough to open the solenoid valve and to energize the ignition control If the switch is not sailing in clean any dust or dirt from the actuator pin Other reasons for the switch not...

Page 16: ...ct it WARNINGS Never connect unit or ignition circuit to 230 volts Never operate unit with glo bar touching burner or any other ground Damage to ignition control will occur Be sure sensor probe never...

Page 17: ...en 2 A Check for voltage 24 volts A C at valve 40 seconds after glo bar begins to glow If voltage present but valve not opening replace valve B If no voltage at valve check brown wire at ignition cont...

Page 18: ...ing probe Be sure probe is positioned in the burner flame and glowing cherry red Check wire and wire connections at probe and ignition control B If wire and wire connections okay check for voltage acr...

Page 19: ...ail Switch Note White 115 V A C White Open WIRING DIAGRAMS Figure 21 Wiring Diagram 40 000 BTU Hr Model Figure 20 Wiring Diagram 25 000 BTU Hr Model Note Use only original replacement parts Thiswillpr...

Page 20: ...inet Insulation top 1 191244 Operating Instructions Decal English 1 191246 Operating Instructions Decal French 1 531010 Warning Decal 1 191263 Nameplate 1 Parts available not shown You must order name...

Page 21: ...91241 Front Cover Trim 1 4 030642 Front Cover Assembly 1 5 100896 Cabinet Assembly 1 6 070511 Cabinet Insulation right and left sides 1 7 120158 Screw 8 x 3 8 2 8 160912 Thermostat includes 2 screws 1...

Page 22: ...25 Limit Switch 1 9 231144 Terminal Block 1 10 121224 Screw 10 x 3 4 2 11 070487 Gasket 1 12 231143 Transformer Assembly 1 13 121252 Screw 10 x 3 8 6 14 020983 Combustion Chamber Heat Shield Assembly...

Page 23: ...070607 Heat Shield Gasket 1 14 020982 Combustion Chamber Heat Shield Assembly 1 15 061663 Wire Clamp 2 16 121252 Screw 10 x 3 8 12 17 230560 Limit Switch 1 KEY PART NO NUMBER DESCRIPTION QTY 18 06256...

Page 24: ...19 of this manual 1 2 3 4 5 6 7 8 9 10 11 12 KEY PART NO NUMBER DESCRIPTION QTY 1 120717 Hex Nut 10 24 2 2 121459 Screw 10 24 x 1 2 2 3 010701 Burner Assembly 1 4 180215 Main Burner Orifice 1 5 12138...

Page 25: ...DESCRIPTION QTY 1 120717 Hex Nut 10 24 4 2 010621 Left Burner Assembly 1 3 010623 Right Burner Assembly 1 4 070591 Manifold Gasket 1 5 171167 Manifold Assembly 1 6 180188 Main Burner Orifice 2 7 1213...

Page 26: ...390260 Blower Housing room air 1 8 121421 Hex Lock Nut 10 24 3 9 050751 Crossover Tube 1 10 121388 Screw 10 x 1 2 4 11 070385 Crossover Tube Gasket 2 12 121227 Screw 10 24 x 1 2 2 13 070362 Universal...

Page 27: ...Cover Assy 1 12 121388 Screw 10 x 1 2 3 13 070420 Combustion Air Crossover Gasket 1 14 390318 Combustion Air and Motor Cover Assembly 1 KEY PART NO NUMBER DESCRIPTION QTY 15 121227 Screw 10 24 x 1 2 2...

Page 28: ...ller in accordance with all local codes and instructions furnished with the unit This warranty does not apply to parts that are not in original condition because of normal wear and tear or parts that...

Reviews: