 Key Instructions:

 

  1.  RST:  Press  RST  key  to  switch  on  and off,  press  the  RST  key on  the 
power-off state once to turn on, on the power-on state, press the RST key 
for three seconds and hold on, then it will be off. 
  2. SET: 
  A: Press the SET key once to enter the temperature control setting, press 

 or 

 button to adjust, press 

 or 

 button for three seconds and hold 

to  enter  the  fast  adjusting  mode,  press  the  SET  key  again  to  exit  setting 
mode. 
  B: Press and hold SET key for three seconds to enter the system menu 
settings, press the 

 or 

 key to select the adjustment menu, press SET 

key  once  to  enter  the  appropriate  parameter  settings,  press 

  or 

  to 

adjust the parameters needed to be modified, after being adjusted, press 
the RST key to exit, or exit as the system delay for 5 seconds. 
 

: Up key 

 

: Down key 

 Operating Instructions:

 

  LED Status Description: 
  The 

WORK

 lights at the left side of the screen is used as working indicator 

lights, flashing is to indicate the delay of cooling or heating, if the LED is 
always on ,it indicates it is on the status of cooling or heating . 
  The 

SET

 light at the left side of the screen lights is used as setting indicator 

lights, if the LED is always on ,it indicates it is on the status of setting. 

Function Instructions:

 

  Press 

RST

 key to open the thermostat, on the running status, press this key 

for 3 seconds, then the thermostat can be turned off. 
 

Cooling, heating function:

 

 

Cooling Mode:

 When the measured temperature is higher than or equal to 

the set value + hysteresis, the relay picks up to start the output; When the 
measured temperature below the set value, the relay off and close the output. 
 

Heating mode:

 When the measured temperature is higher than or equal to 

the set value, the relay off, turn off the output; When the measured 
temperature below the set value - hysteresis, the relay picks up to start the 
output. 

 
Example for Setting: If it is set to heating mode, set the temperature to 25 
degrees, hysteresis is set to 5, then when the measured temperature is 
higher than or equal to 25 degrees, the relay is off, close the output. 
When the temperature is below 20 degrees, pick up the relay again, to 
start the output.   
Example for Setting: If it is set to cooling mode, set the temperature to 25 
degrees, hysteresis is set to 5, then when the measured temperature is 
below 25 degrees, the relay is off, close the output. When the 
temperature is higher than or equal to 30 degrees, pick up the relay again, 
to start the output.   

 Cooling, heating mode setting:

 

  Press "SET" key and hold more than 3 seconds to enter the menu display, the 
screen appears "HC" code, press the "SET" key to display the working mode, 
press the "

" or "

" to adjust the display, C means cooling mode; H means 

heating mode. 

 

Hysteresis function:

 

  Hysteresis setting limits the maximum interval between the opening and 
stopping, this machine minimum interval between the opening and stopping is 

PDF 

文件使用

 "pdfFactory Pro" 

试用版本创建

 

www.fineprint.cn

Summary of Contents for WH7016E

Page 1: ...WH7016E Thermostat Product Manual Shenzhen Willhi Electronics Co Ltd Tel 0755 29539385 Fax 86 0755 2953 9395 Technical support Engineer Tian PDF 文件使用 pdfFactory Pro 试用版本创建 www fineprint cn ...

Page 2: ...y Terminals 7 and 8 Temperature connection sensor Note The load refers to the heating or cooling equipment on control Electrical performance Temperature measurement range 9 9 99 9 Temperature control range 9 9 99 9 Temperature measurement error 0 5 Sensor Type NTC 10K 3435 Control accuracy 1 Working voltage AC DC12V AC220V AC110V Working current 2W Relay contact point current AC 7A 220V Data stora...

Page 3: ...turned off Cooling heating function Cooling Mode When the measured temperature is higher than or equal to the set value hysteresis the relay picks up to start the output When the measured temperature below the set value the relay off and close the output Heating mode When the measured temperature is higher than or equal to the set value the relay off turn off the output When the measured temperatu...

Page 4: ...er on when the measured value above the set value hysteresis value the machine will not immediately start cooling it needs to set the delay time then the machine can run to start cooling once the interval between two cooling is larger than the delay time the machine immediately starts cooling once the interval between two cooling is less than the delay time the machine must run the remaining delay...

Page 5: ...e alarm output relay Thermostat alarm will sound the display alternately shows L and the current temperature Alarm press any key to stop the alarm and relay output low temperature alarm settings Press SET button and hold more than 3 seconds to enter the menu display with or button transferred to the screen appears AL code press the SET key to display the low temperature alarm settings press or key...

Page 6: ...ected with the terminal otherwise it would result in reducing the reliability of machine When connecting the wire please separate power supply relays sensors otherwise it will damage the machine PDF 文件使用 pdfFactory Pro 试用版本创建 www fineprint cn ...

Reviews: