 Key Instructions:

 

  1. RST: Press RST key to switch on and off, press the RST key on the 
power-off state once to turn on, on the power-on state, press the RST key 
for three seconds and hold on, then it will be off. 
 2. SET: 
  A: Press the SET key once to enter the temperature control setting, press 

 or 

 button to adjust, press 

 or 

 button for three seconds and hold 

to enter the fast adjusting mode, press the SET key again to exit setting 
mode. 
  B: Press and hold SET key for three seconds to enter the system menu 
settings, press the 

 or 

 key to select the adjustment menu, press SET 

key once to enter the appropriate parameter settings, press 

 or 

 to 

adjust the parameters needed to be modified, after being adjusted, press 
the RST key to exit, or exit as the system delay for 5 seconds. 
 

: Up key 

 

: Down key 

 Operating Instructions:

 

  LED Status Description: 
 The 

WORK

 lights at the left side of the screen is used as working indicator 

lights, flashing is to indicate the delay of cooling or heating, if the LED is 
always on ,it indicates it is on the status of cooling or heating . 
 The 

SET

 light at the left side of the screen lights is used as setting indicator 

lights, if the LED is always on ,it indicates it is on the status of setting. 

Function Instructions:

 

 Press 

RST

 key to open the thermostat, on the running status, press this key 

for 3 seconds, then the thermostat can be turned off. 
 

Cooling, heating function:

 

 

Cooling Mode:

 When the measured temperature is higher than or equal to 

the set value + hysteresis, the relay picks up to start the output; When the 
measured temperature below the set value, the relay off and close the output. 
 

Heating mode:

 When the measured temperature is higher than or equal to 

the set value, the relay off, turn off the output; When the measured 
temperature below the set value - hysteresis, the relay picks up to start the 
output. 

 
Example for Setting: If it is set to heating mode, set the temperature to 25 
degrees, hysteresis is set to 5, then when the measured temperature is 
higher than or equal to 25 degrees, the relay is off, close the output. 
When the temperature is below 20 degrees, pick up the relay again, to 
start the output.   
Example for Setting: If it is set to cooling mode, set the temperature to 25 
degrees, hysteresis is set to 5, then when the measured temperature is 
below 25 degrees, the relay is off, close the output. When the 
temperature is higher than or equal to 30 degrees, pick up the relay again, 
to start the output.   

 Cooling, heating mode setting:

 

  Press "SET" key and hold more than 3 seconds to enter the menu display, the 
screen appears "HC" code, press the "SET" key to display the working mode, 
press the "

" or "

" to adjust the display, C means cooling mode; H means 

heating mode. 

 

Hysteresis function:

 

  Hysteresis setting limits the maximum interval between the opening and 
stopping, this machine minimum interval between the opening and stopping is 

Summary of Contents for WH7016C

Page 1: ...WH7016C Thermostat Product Manual ...

Page 2: ...hort circuit the user can not modify Terminals 7 and 8 Temperature connection sensor Note The load refers to the heating or cooling equipment on control Electrical performance Temperature measurement range 50 110 Temperature control range 50 110 Temperature measurement error 0 5 Sensor Type NTC 10K 3435 Control accuracy 1 Working voltage AC DC12V Working current 2W Relay contact point current AC 7...

Page 3: ...n the thermostat can be turned off Cooling heating function Cooling Mode When the measured temperature is higher than or equal to the set value hysteresis the relay picks up to start the output When the measured temperature below the set value the relay off and close the output Heating mode When the measured temperature is higher than or equal to the set value the relay off turn off the output Whe...

Page 4: ...oling mode the first power on when the measured value above the set value hysteresis value the machine will not immediately start cooling it needs to set the delay time then the machine can run to start cooling once the interval between two cooling is larger than the delay time the machine immediately starts cooling once the interval between two cooling is less than the delay time the machine must...

Page 5: ...minimum set limit 50 110 50 HS The maximum set limit 50 110 110 CA Temperature calibration 5 5 0 PT Delay time 0 10 1 Minutes fault tips 1 When the sensor disconnected the screen displays and close the heating wire 2 When the sensor detects the temperature is below 50 degrees the screen displays LLL 3 When the sensor detects a temperature higher than 110 degrees the screen displays HHH Caution for...

Reviews: