Faults
Causes
Measures
No output signal
Cable break
Check the continuity
Deviating zero point signal
Overload safety exceeded
Observe the permissible overload safety
Deviating zero point signal
Too high/low working temperature
Observe the permissible temperatures
Constant output signal upon change in
pressure
Mechanical overload caused by overpres-
sure
Replace instrument; if it fails repeatedly,
contact the manufacturer
Signal span varies
EMC interference sources in the environ-
ment; for example, frequency converter
Shield instrument; cable shield; remove
source of interference
Signal span varies/inaccurate
Too high/low working temperature
Observe the permissible temperatures
Signal span drops/too small
Mechanical overload caused by overpres-
sure
Replace instrument; if it fails repeatedly,
contact the manufacturer