4.  Transport, packaging and storage

4.1  Transport

Check the instrument for any damage that may have been caused by transport.

Obvious damage must be reported immediately.

CAUTION!

Damage through improper transport

With improper transport, a high level of damage to property can occur.

 

When unloading packed goods upon delivery as well as during internal 

transport, proceed carefully and observe the symbols on the packaging.

 

With internal transport, observe the instructions in chapter 4.2 “Packaging 

and storage”.

If the instrument is transported from a cold into a warm environment, the formation of 

condensation may result in instrument malfunction. Before putting it back into operation, 

wait for the instrument temperature and the room temperature to equalise.

4.2  Packaging and storage

Do not remove packaging until just before mounting.

Keep the packaging as it will provide optimum protection during transport (e.g. change 

in installation site, sending for repair).

Permissible conditions at the place of storage:

 

Storage temperature: -50 ... +60 °C [-58 ... +140 °F]

 

Humidity: 35 ... 85 % relative humidity (no condensation)

Avoid exposure to the following factors:

 

Direct sunlight or proximity to hot objects

 

Mechanical vibration, mechanical shock (putting it down hard)

 

Soot, vapour, dust and corrosive gases

 

Hazardous environments, flammable atmospheres

Store the instrument in its original packaging in a location that fulfils the conditions listed 

above.

5.  Commissioning, operation

Before installation, commissioning and operation, ensure that the appropriate instru-

ment has been selected in terms of design and specific measuring conditions.
Tools: 6.5 mm socket wrench, cross-head screwdreiver, 20 mm open-ended spanner, 

6 mm Allen key

5.1  Requirements at the measuring point

 

The process pressure must not exceed the specified maximum operating pressure.

 

Permissible ambient and medium temperatures remain within the performance 

limits.

 

Protected from weather influences.

 

Any vibrations or shocks which occur must not exceed accelerations of 

1 g (9.81 m/s

2

) within a frequency range of 10 ... 150 Hz.

 

The measuring line and the process connection must be designed such that no 

mechanical loads can occur on the instrument in the entire permissible ambient and 

medium temperature ranges.

 

Sealing faces are clean and undamaged.

 

Maintain clearance for blow-out device of > 20 mm.

 

Sufficient space for a safe electrical installation.

→ For performance limits see chapter 9 “Specifications”

5.2  Mechanical mounting

 

After unpacking the instrument, a visual inspection for damage must be carried out.

 

Mounting is only permitted in the depressurised state. Reliably depressurise the 

instrument using the available valves and protective devices.

 

Use seals suitable for the process connection provided.

 

When screwing the instruments in, the force required for sealing must not be applied 

through the case, but only through the spanner flats provided for this purpose on the 

process connection, and using a suitable tool. The tightening torque is dependent on 

the selected process connection.

 

After screwing in, make sure that no damage or cracks have occurred at the process 

connection.

Summary of Contents for PSM-700

Page 1: ...ty and environmental criteria during production Our management systems are certified to ISO 9001 These operating instructions contain important information on handling the instru ment Working safely requires that all safety instructions and work instructions are observed Observe the relevant local accident prevention regulations and general safety regulations for the instrument s range of use The ...

Page 2: ... of any damage caused by using the product contrary to its intended use non compliance with these operating instructions assignment of insufficiently qualified skilled personnel or unauthorised modifications to the instrument The general terms and conditions contained in the sales documentation shall apply Subject to technical modifications Further information Internet address www wika de www wika...

Page 3: ... that lie within its technical performance limits e g max ambient temperature material compatibility For performance limits see chapter 9 Specifications This instrument is not permitted to be used in hazardous areas The instrument has been designed and built solely for the intended use described here and may only be used accordingly The manufacturer shall not be liable for claims of any type based...

Page 4: ...its original packaging in a location that fulfils the conditions listed above 5 Commissioning operation Before installation commissioning and operation ensure that the appropriate instru ment has been selected in terms of design and specific measuring conditions Tools 6 5 mm socket wrench cross head screwdreiver 20 mm open ended spanner 6 mm Allen key 5 1 Requirements at the measuring point The pr...

Page 5: ...operty and the environment Should a failure occur aggressive media with extremely high temperature and under high pressure or vacuum may be present at the instrument For these media in addition to all standard regulations the appropriate existing codes or regulations must also be followed 1 Remove 4 screws and open cover 2 Remove the cover s of the electrical connection s 3 Fit suitable cable glan...

Page 6: ...ch point Carry out switch point setting with matching test assembly see chapter 5 2 Vibrations Decouple the instrument mechanically Short circuit Moisture in the instrument Only use in ambient conditions for which the ingress protection is suitable Contact chatter repeated short duration opening and closing Vibrations Decouple the instrument mechanically 5 5 Setting of the switch differential opti...

Page 7: ...elow 1 Before cleaning correctly disconnect the instrument from the pressure supply and switch the load circuit off 2 Use the requisite protective equipment 3 Clean the instrument with a moist cloth Electrical connections must not come into contact with moisture CAUTION Damage to the instrument Improper cleaning may lead to damage to the instrument Do not use any aggressive cleaning agents Do not ...

Page 8: ...s I per IEC 61010 1 2010 case grounded with protective conductor overvoltage category II pollution degree 2 Contact version Switch type Electrical rating AC Electrical rating DC Resistive load Inductive load Resistive load Inductive load 125 V 250 V 125 V 250 V 30 V 125 V 250 V 30 V 125 V 250 V Switch differential Fixed SPDT 10 A 10 A 10 A 10 A 2 A 0 4 A 0 2 A 1 A 0 03 A 0 02 A DPDT 15 A 10 A 10 A...

Reviews: